# B1 — Programming Object Inventory
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS (AB-Run-2)"
  generated_from: A1-io-list.yaml + A2-equipment-takeoff.yaml
  generator: _playbook/tools/generate-b1-b3-programming-and-commissioning.py
  rates:
    hrs_per_point_object: 0.1
    hrs_per_control_loop: 2.0
    hrs_per_alarm: 0.15
    hrs_per_trend: 0.1
    hrs_per_schedule: 0.5
    hrs_per_report: 1.5
summary:
  point_database_objects: 462
  control_loops: 33
  alarm_definitions: 63
  trend_logs: 332
  schedules: 8
  scheduled_reports: 10
  total_objects: 908
programming_hours:
  point_database_setup: 46.2
  control_logic_per_equipment: 66.0
  alarms: 9.4
  schedules: 4.0
  reports: 15.0
  trends: 33.2
  total_programming_hours: 173.8
  person_days_at_8hr: 21.7
control_loop_inventory:
- equipment: AHU-2F-A
  equipment_class: AHU (Chilled-Water-Served)
  location: 2F Common Public
- equipment: AHU-2F-B
  equipment_class: AHU (Chilled-Water-Served)
  location: 2F Common Public
- equipment: AHU-3F-AM
  equipment_class: AHU (Chilled-Water-Served)
  location: 3F Amenity
- equipment: AHU-CASINO-1
  equipment_class: AHU (Modulating CHW-served)
  location: Ground Floor Casino
- equipment: AHU-CASINO-2
  equipment_class: AHU (Modulating CHW-served)
  location: Ground Floor Casino
- equipment: AHU-GF-CASINO
  equipment_class: AHU (Modulating CHW-served)
  location: Ground Floor Casino Lobby
- equipment: AHU-GF-LOB
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor Lobby
- equipment: AHU-GF-REST
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor Restaurant
- equipment: BLR-1
  equipment_class: Steam Boiler
  location: Lower Ground Boiler Room
- equipment: BLR-2
  equipment_class: Steam Boiler
  location: Lower Ground Boiler Room
- equipment: BTU-CHW-MAIN
  equipment_class: BTU Meter
  location: 2F Chiller Plant Room
- equipment: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  location: 2F Chiller Plant Room
- equipment: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  location: 2F Chiller Plant Room
- equipment: CHW-BYP
  equipment_class: CHW Bypass Header
  location: 2F Chiller Plant Room
- equipment: CHWP-1
  equipment_class: Primary CHW Pump
  location: 2F Chiller Plant Room
- equipment: CHWP-2
  equipment_class: Primary CHW Pump
  location: 2F Chiller Plant Room
- equipment: CHWP-3
  equipment_class: Primary CHW Pump (Standby)
  location: 2F Chiller Plant Room
- equipment: CT-1
  equipment_class: Cooling Tower
  location: Roofdeck Cooling Tower
- equipment: CT-2
  equipment_class: Cooling Tower
  location: Roofdeck Cooling Tower
- equipment: CWP-1
  equipment_class: Condenser Water Pump
  location: 2F Chiller Plant Room
- equipment: CWP-2
  equipment_class: Condenser Water Pump
  location: 2F Chiller Plant Room
- equipment: CWP-3
  equipment_class: Condenser Water Pump
  location: 2F Chiller Plant Room
- equipment: DOAS-2F
  equipment_class: DOAS Unit
  location: 2F Common Public
- equipment: DOAS-RD1
  equipment_class: DOAS Unit
  location: Roofdeck DOAS
- equipment: DOAS-RD2
  equipment_class: DOAS Unit
  location: Roofdeck DOAS
- equipment: HP-LG-1
  equipment_class: Heat Pump
  location: Lower Ground Calorifier Room
- equipment: HP-ROOF-1
  equipment_class: Heat Pump
  location: Roofdeck DOAS
- equipment: HW-PUMP-LG-1
  equipment_class: Recirculating Pump
  location: Lower Ground Calorifier Room
- equipment: HW-PUMP-LG-2
  equipment_class: Recirculating Pump
  location: Lower Ground Calorifier Room
- equipment: HW-PUMP-ROOF-1
  equipment_class: Recirculating Pump
  location: Roofdeck DOAS
- equipment: PAHU-2F
  equipment_class: Precooled Air Handling Unit
  location: 2F Common Public
- equipment: PAHU-BSMT
  equipment_class: Precooled Air Handling Unit
  location: Basement BOH
- equipment: PAHU-ROOF
  equipment_class: Precooled Air Handling Unit
  location: Roofdeck DOAS
notes:
- 'Point database objects: every AI/AO/DI/DO/HLI in A1 becomes one programmable point. 462 total.'
- 'Control loops: one per equipment with active control. 33 loops covering chillers, pumps, fans, AHU/DOAS, boilers.'
- 'Alarms: 1 per critical equipment + system-wide alarms (network down, server fail, UPS, etc.).'
- 'Trends: subset of points logged for historical analysis. Defaults: 100% AO/DO, 100% AI, 40% DI, 70% HLI.'
- 'Schedules: occupancy weekday/weekend/holiday + plant on/off + lighting + setbacks.'
- 'Reports: daily/weekly/monthly energy + runtime + alarm summary.'