# A3 — Cable Schedule
# Generated from A1-io-list.yaml; lengths per A-001
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS (AB-Run-2)"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a3-cable-schedule.py
  assumptions:
  - 'A-001: 30 m average panel-to-device run; 80 m trunk per floor'
  - Cable conductor count = (points + 2 spare), rounded up to standard 4/6/8/12 sizes
  - Cat6 for all BACnet/IP network drops
  - BACnet MS/TP backbone interconnects all BMS panels (refine after Q-008)
  - 240V single-phase power feed to each BMS panel @ 30 m default length
summary:
  total_field_cable_runs: 96
  total_field_cable_length_m: 1870
  total_trunk_cable_length_m: 730
  total_power_feed_length_m: 232
  grand_total_cable_length_m: 2832
  field_cable_by_type_m:
    "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)": 781
    "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)": 507
    "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)": 384
    "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)": 198
  field_cable_by_panel_m:
    PNL-AIR-2F: 15
    PNL-AIR-3F: 5
    PNL-CASINO-GF: 11
    PNL-AIR-GF: 9
    PNL-BLR-LG: 5
    PNL-PL-LG: 7
    PNL-AIR-ROOF: 13
    PNL-CH-PLANT-2F: 17
    PNL-CT-ROOF: 8
    PNL-AIR-BSMT: 5
    PNL-PM-LG: 1
field_cables:
- id: C0001
  from: PNL-AIR-2F
  to: AHU-2F-A (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0233
  - P0234
  - P0235
  - P0236
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0002
  from: PNL-AIR-2F
  to: AHU-2F-A (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0237
  - P0238
  - P0241
  - P0242
  - P0243
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0003
  from: PNL-AIR-2F
  to: AHU-2F-A (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0239
  - P0240
  - P0245
  - P0246
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0004
  from: PNL-AIR-2F
  to: AHU-2F-B (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0247
  - P0248
  - P0249
  - P0250
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0005
  from: PNL-AIR-2F
  to: AHU-2F-B (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0251
  - P0252
  - P0255
  - P0256
  - P0257
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0006
  from: PNL-AIR-2F
  to: AHU-2F-B (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0253
  - P0254
  - P0259
  - P0260
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0007
  from: PNL-AIR-3F
  to: AHU-3F-AM (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 3F Amenity
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0334
  - P0335
  - P0336
  - P0337
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0008
  from: PNL-AIR-3F
  to: AHU-3F-AM (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 3F Amenity
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0338
  - P0339
  - P0342
  - P0343
  - P0344
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0009
  from: PNL-AIR-3F
  to: AHU-3F-AM (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: 3F Amenity
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0340
  - P0341
  - P0346
  - P0347
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0010
  from: PNL-CASINO-GF
  to: AHU-CASINO-1 (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0303
  - P0304
  - P0305
  - P0316
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0011
  from: PNL-CASINO-GF
  to: AHU-CASINO-1 (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0306
  - P0307
  - P0310
  - P0311
  - P0312
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0012
  from: PNL-CASINO-GF
  to: AHU-CASINO-1 (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0308
  - P0309
  - P0314
  - P0315
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0013
  from: PNL-CASINO-GF
  to: AHU-CASINO-2 (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0317
  - P0318
  - P0319
  - P0330
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0014
  from: PNL-CASINO-GF
  to: AHU-CASINO-2 (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0320
  - P0321
  - P0324
  - P0325
  - P0326
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0015
  from: PNL-CASINO-GF
  to: AHU-CASINO-2 (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0322
  - P0323
  - P0328
  - P0329
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0016
  from: PNL-CASINO-GF
  to: AHU-GF-CASINO (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: Air Conditioning
  location: Ground Floor Casino Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0289
  - P0290
  - P0291
  - P0302
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0017
  from: PNL-CASINO-GF
  to: AHU-GF-CASINO (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: Air Conditioning
  location: Ground Floor Casino Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0292
  - P0293
  - P0296
  - P0297
  - P0298
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0018
  from: PNL-CASINO-GF
  to: AHU-GF-CASINO (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: Air Conditioning
  location: Ground Floor Casino Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0294
  - P0295
  - P0300
  - P0301
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0019
  from: PNL-AIR-GF
  to: AHU-GF-LOB (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: Ground Floor Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0261
  - P0262
  - P0263
  - P0264
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0020
  from: PNL-AIR-GF
  to: AHU-GF-LOB (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: Ground Floor Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0265
  - P0266
  - P0269
  - P0270
  - P0271
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0021
  from: PNL-AIR-GF
  to: AHU-GF-LOB (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: Ground Floor Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0267
  - P0268
  - P0273
  - P0274
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0022
  from: PNL-AIR-GF
  to: AHU-GF-REST (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: Ground Floor Restaurant
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0275
  - P0276
  - P0277
  - P0278
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0023
  from: PNL-AIR-GF
  to: AHU-GF-REST (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: Ground Floor Restaurant
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0279
  - P0280
  - P0283
  - P0284
  - P0285
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0024
  from: PNL-AIR-GF
  to: AHU-GF-REST (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: Air Conditioning
  location: Ground Floor Restaurant
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0281
  - P0282
  - P0287
  - P0288
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0025
  from: PNL-BLR-LG
  to: BLR-1 (BMS Contractor)
  equipment_class: Steam Boiler
  system: Boiler
  location: Lower Ground Boiler Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 10
  length_method: measured
  length_basis: EE-03 + BMS-01 (boiler @ Lower Ground)
  carries_io_points: 6
  carries_point_ids:
  - P0395
  - P0396
  - P0397
  - P0398
  - P0409
  - '...'
  notes: 6 I/O points carried, 8C cable; length 10 m (measured)
- id: C0026
  from: PNL-BLR-LG
  to: BLR-1 (Equipment Supplier)
  equipment_class: Steam Boiler
  system: Boiler
  location: Lower Ground Boiler Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 10
  carries_point_ids:
  - P0399
  - P0400
  - P0401
  - P0402
  - P0403
  - '...'
  notes: 10 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0027
  from: PNL-BLR-LG
  to: BLR-2 (BMS Contractor)
  equipment_class: Steam Boiler
  system: Boiler
  location: Lower Ground Boiler Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 12
  length_method: measured
  length_basis: EE-03 + BMS-01
  carries_io_points: 6
  carries_point_ids:
  - P0411
  - P0412
  - P0413
  - P0414
  - P0425
  - '...'
  notes: 6 I/O points carried, 8C cable; length 12 m (measured)
- id: C0028
  from: PNL-BLR-LG
  to: BLR-2 (Equipment Supplier)
  equipment_class: Steam Boiler
  system: Boiler
  location: Lower Ground Boiler Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 10
  carries_point_ids:
  - P0415
  - P0416
  - P0417
  - P0418
  - P0419
  - '...'
  notes: 10 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0029
  from: PNL-PL-LG
  to: CALOR-LG (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: Hot Water
  location: Lower Ground Calorifier Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 8
  length_method: measured
  length_basis: EE-03 + BMS-03 calorifier diagram
  carries_io_points: 1
  carries_point_ids:
  - P0375
  notes: 1 I/O points carried, 4C cable; length 8 m (measured)
- id: C0030
  from: PNL-AIR-ROOF
  to: CALOR-ROOF (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: Hot Water
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0376
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0031
  from: PNL-CH-PLANT-2F
  to: CH-1 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 15
  length_method: measured
  length_basis: EE-09 grid F-3 (chiller skid) + BMS-01 chiller layout
  carries_io_points: 7
  carries_point_ids:
  - P0001
  - P0002
  - P0003
  - P0004
  - P0005
  - '...'
  notes: 7 I/O points carried, 12C cable; length 15 m (measured)
- id: C0032
  from: PNL-CH-PLANT-2F
  to: CH-1 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 2
  carries_point_ids:
  - P0008
  - P0009
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0033
  from: PNL-CH-PLANT-2F
  to: CH-2 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 18
  length_method: measured
  length_basis: EE-09 grid F-4 + BMS-01
  carries_io_points: 7
  carries_point_ids:
  - P0029
  - P0030
  - P0031
  - P0032
  - P0033
  - '...'
  notes: 7 I/O points carried, 12C cable; length 18 m (measured)
- id: C0034
  from: PNL-CH-PLANT-2F
  to: CH-2 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 2
  carries_point_ids:
  - P0036
  - P0037
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0035
  from: PNL-CH-PLANT-2F
  to: CHW-BYP (BMS Contractor)
  equipment_class: CHW Bypass Header
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 10
  length_method: measured
  length_basis: BMS-01 control diagram + EE-09
  carries_io_points: 4
  carries_point_ids:
  - P0094
  - P0095
  - P0096
  - P0097
  notes: 4 I/O points carried, 6C cable; length 10 m (measured)
- id: C0036
  from: PNL-CH-PLANT-2F
  to: CHW-RET-HDR (BMS Contractor)
  equipment_class: CHW Return Main Header
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 8
  length_method: measured
  length_basis: BMS-01 + EE-09 grid F-2
  carries_io_points: 2
  carries_point_ids:
  - P0092
  - P0093
  notes: 2 I/O points carried, 4C cable; length 8 m (measured)
- id: C0037
  from: PNL-CH-PLANT-2F
  to: CHW-SUP-HDR (BMS Contractor)
  equipment_class: CHW Supply Main Header
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 8
  length_method: measured
  length_basis: BMS-01 + EE-09 grid F-2 (header gallery)
  carries_io_points: 2
  carries_point_ids:
  - P0090
  - P0091
  notes: 2 I/O points carried, 4C cable; length 8 m (measured)
- id: C0038
  from: PNL-CH-PLANT-2F
  to: CHWP-1 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 10
  length_method: measured
  length_basis: EE-09 grid E-3 (CHW pump skid)
  carries_io_points: 7
  carries_point_ids:
  - P0057
  - P0058
  - P0059
  - P0060
  - P0061
  - '...'
  notes: 7 I/O points carried, 12C cable; length 10 m (measured)
- id: C0039
  from: PNL-CH-PLANT-2F
  to: CHWP-2 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 11
  length_method: measured
  length_basis: EE-09 grid E-3
  carries_io_points: 7
  carries_point_ids:
  - P0064
  - P0065
  - P0066
  - P0067
  - P0068
  - '...'
  notes: 7 I/O points carried, 12C cable; length 11 m (measured)
- id: C0040
  from: PNL-CH-PLANT-2F
  to: CHWP-3 (Equipment Supplier)
  equipment_class: Primary CHW Pump (Standby)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 12
  length_method: measured
  length_basis: EE-09 grid E-3
  carries_io_points: 7
  carries_point_ids:
  - P0071
  - P0072
  - P0073
  - P0074
  - P0075
  - '...'
  notes: 7 I/O points carried, 12C cable; length 12 m (measured)
- id: C0041
  from: PNL-CT-ROOF
  to: CT-1 (BMS Contractor)
  equipment_class: Cooling Tower
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 4
  carries_point_ids:
  - P0108
  - P0109
  - P0110
  - P0111
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0042
  from: PNL-CT-ROOF
  to: CT-1 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 14
  length_method: measured
  length_basis: BMS-03 cooling-tower diagram + roofdeck plan inferred
  carries_io_points: 3
  carries_point_ids:
  - P0105
  - P0106
  - P0107
  notes: 3 I/O points carried, 6C cable; length 14 m (measured)
- id: C0043
  from: PNL-CT-ROOF
  to: CT-2 (BMS Contractor)
  equipment_class: Cooling Tower
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 4
  carries_point_ids:
  - P0115
  - P0116
  - P0117
  - P0118
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0044
  from: PNL-CT-ROOF
  to: CT-2 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 16
  length_method: measured
  length_basis: BMS-03 + roofdeck layout
  carries_io_points: 3
  carries_point_ids:
  - P0112
  - P0113
  - P0114
  notes: 3 I/O points carried, 6C cable; length 16 m (measured)
- id: C0045
  from: PNL-CT-ROOF
  to: CT-COMMON (BMS Contractor)
  equipment_class: Cooling Tower (Common)
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 12
  length_method: measured
  length_basis: BMS-03
  carries_io_points: 4
  carries_point_ids:
  - P0119
  - P0120
  - P0121
  - P0122
  notes: 4 I/O points carried, 6C cable; length 12 m (measured)
- id: C0046
  from: PNL-CT-ROOF
  to: CT-COMMON (ME Contractor)
  equipment_class: Cooling Tower (Common)
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 2
  carries_point_ids:
  - P0123
  - P0124
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0047
  from: PNL-CT-ROOF
  to: CW-HDR (BMS Contractor)
  equipment_class: Condenser Water Header
  system: Condenser Water Loop
  location: Roofdeck Cooling Tower
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 2
  carries_point_ids:
  - P0098
  - P0099
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0048
  from: PNL-CH-PLANT-2F
  to: CWP-1 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: Condenser Water Loop
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 13
  length_method: measured
  length_basis: EE-09 grid D-3 (CW pump skid)
  carries_io_points: 4
  carries_point_ids:
  - P0078
  - P0079
  - P0080
  - P0081
  notes: 4 I/O points carried, 6C cable; length 13 m (measured)
- id: C0049
  from: PNL-CH-PLANT-2F
  to: CWP-2 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: Condenser Water Loop
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 13
  length_method: measured
  length_basis: EE-09 grid D-3
  carries_io_points: 4
  carries_point_ids:
  - P0082
  - P0083
  - P0084
  - P0085
  notes: 4 I/O points carried, 6C cable; length 13 m (measured)
- id: C0050
  from: PNL-CH-PLANT-2F
  to: CWP-3 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: Condenser Water Loop
  location: 2F Chiller Plant Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 14
  length_method: measured
  length_basis: EE-09 grid D-3
  carries_io_points: 4
  carries_point_ids:
  - P0086
  - P0087
  - P0088
  - P0089
  notes: 4 I/O points carried, 6C cable; length 14 m (measured)
- id: C0051
  from: PNL-AIR-2F
  to: DOAS-2F (BMS Contractor)
  equipment_class: DOAS Unit
  system: Ventilation
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 6
  carries_point_ids:
  - P0173
  - P0174
  - P0175
  - P0178
  - P0179
  - '...'
  notes: 6 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0052
  from: PNL-AIR-2F
  to: DOAS-2F (Equipment Supplier)
  equipment_class: DOAS Unit
  system: Ventilation
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 16
  conductor_count_specified: 16
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 14
  carries_point_ids:
  - P0176
  - P0177
  - P0183
  - P0184
  - P0185
  - '...'
  notes: 14 I/O points carried, 16C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0053
  from: PNL-AIR-2F
  to: DOAS-2F (ME Contractor)
  equipment_class: DOAS Unit
  system: Ventilation
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 4
  carries_point_ids:
  - P0181
  - P0182
  - P0195
  - P0196
  notes: 4 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0054
  from: PNL-AIR-ROOF
  to: DOAS-RD1 (BMS Contractor)
  equipment_class: DOAS Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 6
  carries_point_ids:
  - P0125
  - P0126
  - P0127
  - P0130
  - P0131
  - '...'
  notes: 6 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0055
  from: PNL-AIR-ROOF
  to: DOAS-RD1 (Equipment Supplier)
  equipment_class: DOAS Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 16
  conductor_count_specified: 16
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 14
  carries_point_ids:
  - P0128
  - P0129
  - P0135
  - P0136
  - P0137
  - '...'
  notes: 14 I/O points carried, 16C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0056
  from: PNL-AIR-ROOF
  to: DOAS-RD1 (ME Contractor)
  equipment_class: DOAS Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 4
  carries_point_ids:
  - P0133
  - P0134
  - P0147
  - P0148
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0057
  from: PNL-AIR-ROOF
  to: DOAS-RD2 (BMS Contractor)
  equipment_class: DOAS Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 6
  carries_point_ids:
  - P0149
  - P0150
  - P0151
  - P0154
  - P0155
  - '...'
  notes: 6 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0058
  from: PNL-AIR-ROOF
  to: DOAS-RD2 (Equipment Supplier)
  equipment_class: DOAS Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 16
  conductor_count_specified: 16
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 14
  carries_point_ids:
  - P0152
  - P0153
  - P0159
  - P0160
  - P0161
  - '...'
  notes: 14 I/O points carried, 16C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0059
  from: PNL-AIR-ROOF
  to: DOAS-RD2 (ME Contractor)
  equipment_class: DOAS Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 4
  carries_point_ids:
  - P0157
  - P0158
  - P0171
  - P0172
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0060
  from: PNL-AIR-2F
  to: EAS-GEN-2F (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: Exhaust
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0363
  - P0364
  - P0365
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0061
  from: PNL-AIR-3F
  to: EAS-GEN-3F (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: Exhaust
  location: 3F Amenity
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0369
  - P0370
  - P0371
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0062
  from: PNL-AIR-BSMT
  to: EAS-GEN-BSMT (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: Exhaust
  location: Basement BOH
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0351
  - P0352
  - P0353
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0063
  from: PNL-AIR-GF
  to: EAS-GEN-GF (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: Exhaust
  location: Ground Floor Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0357
  - P0358
  - P0359
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0064
  from: PNL-AIR-ROOF
  to: EAS-GEN-ROOF (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: Exhaust
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0372
  - P0373
  - P0374
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0065
  from: PNL-AIR-2F
  to: EAS-TOILET-2F (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: Exhaust
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0360
  - P0361
  - P0362
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0066
  from: PNL-AIR-3F
  to: EAS-TOILET-3F (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: Exhaust
  location: 3F Amenity
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0366
  - P0367
  - P0368
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0067
  from: PNL-AIR-BSMT
  to: EAS-TOILET-BSMT (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: Exhaust
  location: Basement BOH
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0348
  - P0349
  - P0350
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0068
  from: PNL-AIR-GF
  to: EAS-TOILET-GF (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: Exhaust
  location: Ground Floor Lobby
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0354
  - P0355
  - P0356
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0069
  from: PNL-PL-LG
  to: HP-LG-1 (Equipment Supplier)
  equipment_class: Heat Pump
  system: Hot Water
  location: Lower Ground Calorifier Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0380
  - P0381
  - P0382
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0070
  from: PNL-AIR-ROOF
  to: HP-ROOF-1 (Equipment Supplier)
  equipment_class: Heat Pump
  system: Hot Water
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0383
  - P0384
  - P0385
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0071
  from: PNL-PL-LG
  to: HW-HEADERS-LG (BMS Contractor)
  equipment_class: Hot Water Header Set
  system: Hot Water
  location: Lower Ground Calorifier Room
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 10
  length_method: measured
  length_basis: EE-03 + BMS-03
  carries_io_points: 3
  carries_point_ids:
  - P0377
  - P0378
  - P0379
  notes: 3 I/O points carried, 6C cable; length 10 m (measured)
- id: C0072
  from: PNL-PL-LG
  to: HW-PUMP-LG-1 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: Hot Water
  location: Lower Ground Calorifier Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0386
  - P0387
  - P0388
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0073
  from: PNL-PL-LG
  to: HW-PUMP-LG-2 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: Hot Water
  location: Lower Ground Calorifier Room
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0389
  - P0390
  - P0391
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0074
  from: PNL-AIR-ROOF
  to: HW-PUMP-ROOF-1 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: Hot Water
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0392
  - P0393
  - P0394
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0075
  from: PNL-CASINO-GF
  to: OZ-CASINO-1 (Equipment Supplier)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: Casino Air Conditioning
  location: Ground Floor Casino
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0331
  - P0332
  - P0333
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0076
  from: PNL-AIR-2F
  to: PAHU-2F (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 3
  carries_point_ids:
  - P0209
  - P0210
  - P0213
  notes: 3 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0077
  from: PNL-AIR-2F
  to: PAHU-2F (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 7
  carries_point_ids:
  - P0211
  - P0212
  - P0214
  - P0215
  - P0216
  - '...'
  notes: 7 I/O points carried, 12C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0078
  from: PNL-AIR-2F
  to: PAHU-2F (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: 2F Common Public
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 2
  carries_point_ids:
  - P0219
  - P0220
  notes: 2 I/O points carried, 4C cable; length 30 m (typical_range:boh_same_floor_field)
- id: C0079
  from: PNL-AIR-BSMT
  to: PAHU-BSMT (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: Basement BOH
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0221
  - P0222
  - P0225
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0080
  from: PNL-AIR-BSMT
  to: PAHU-BSMT (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: Basement BOH
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 7
  carries_point_ids:
  - P0223
  - P0224
  - P0226
  - P0227
  - P0228
  - '...'
  notes: 7 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0081
  from: PNL-AIR-BSMT
  to: PAHU-BSMT (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: Basement BOH
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 2
  carries_point_ids:
  - P0231
  - P0232
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0082
  from: PNL-AIR-ROOF
  to: PAHU-ROOF (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 3
  carries_point_ids:
  - P0197
  - P0198
  - P0201
  notes: 3 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0083
  from: PNL-AIR-ROOF
  to: PAHU-ROOF (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 7
  carries_point_ids:
  - P0199
  - P0200
  - P0202
  - P0203
  - P0204
  - '...'
  notes: 7 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0084
  from: PNL-AIR-ROOF
  to: PAHU-ROOF (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: Ventilation
  location: Roofdeck DOAS
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 2
  carries_point_ids:
  - P0207
  - P0208
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0085
  from: PNL-CH-PLANT-2F
  to: CH-1 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0010
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0086
  from: PNL-CH-PLANT-2F
  to: CH-2 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0038
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0087
  from: PNL-CH-PLANT-2F
  to: BTU-CHW-MAIN (Network)
  equipment_class: BTU Meter
  system: Chilled Water Plant
  location: 2F Chiller Plant Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0100
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0088
  from: PNL-PM-LG
  to: PM-MAIN-LG (Network)
  equipment_class: Multifunction Power Meter (Main)
  system: Power Monitoring
  location: Lower Ground Main Switchgear
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0427
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0089
  from: PNL-CH-PLANT-2F
  to: PM-CHILLER (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: 2F Chiller Plant Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0435
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0090
  from: PNL-CT-ROOF
  to: PM-COOLING (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: Roofdeck Cooling Tower
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0440
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0091
  from: PNL-AIR-2F
  to: PM-AIR-2F (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: 2F Common Public
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 1
  carries_point_ids:
  - P0445
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 30 m (typical_range:boh_same_floor_field)"
- id: C0092
  from: PNL-AIR-GF
  to: PM-AIR-GF (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 1
  carries_point_ids:
  - P0450
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 30 m (typical_range:boh_same_floor_field)"
- id: C0093
  from: PNL-CASINO-GF
  to: PM-CASINO (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: Ground Floor Casino
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  length_method: typical_range:boh_same_floor_field
  length_basis: 'Hotel BOH zone: panel-to-equipment via above-ceiling tray ~22 m horizontal + 4 m vertical drops + 4 m service loops. Confirmed against EE-06 GF and EE-09 2F BOH coverage.'
  carries_io_points: 1
  carries_point_ids:
  - P0455
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 30 m (typical_range:boh_same_floor_field)"
- id: C0094
  from: PNL-BLR-LG
  to: PM-BOILER (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: Lower Ground Boiler Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0460
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0095
  from: PNL-PL-LG
  to: PM-PLUMB (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: Lower Ground Calorifier Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0465
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0096
  from: PNL-PL-LG
  to: PM-FIREPMP (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: Power Monitoring
  location: Lower Ground Boiler Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: "Industry typical 8\u201315 m for in-room plant cabling (panel drop ~2 m + horizontal tray ~6\u201310 m + termination service loops ~2 m). Midpoint of range chosen for proposal-stage estimate."
  carries_io_points: 1
  carries_point_ids:
  - P0470
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
trunk_cables:
- id: T0097
  from: BMS Server Room (head-end)
  to: All BMS panels at 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for 2nd Floor \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0098
  from: BMS Server Room (head-end)
  to: All BMS panels at Basement
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Basement \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0099
  from: BMS Server Room (head-end)
  to: All BMS panels at Ground
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Ground \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0100
  from: BMS Server Room (head-end)
  to: All BMS panels at Lower Ground
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Lower Ground \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0101
  from: BMS Server Room (head-end)
  to: All BMS panels at Roofdeck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Roofdeck \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0102
  from: BMS Server Room (head-end)
  to: All BMS panel controllers (MS/TP daisy-chain or branched)
  cable_type: "BACnet MS/TP shielded twisted-pair trunk, 1pr \xD7 22 AWG low-cap"
  length_m: 330
  notes: "MS/TP backbone interconnecting 11 BMS panels \u2014 refine after Q-008 layout review"
panel_power_feeds:
- id: P0103
  from: Local panelboard / EE-supplied feeder
  to: "PNL-AIR-2F \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0104
  from: Local panelboard / EE-supplied feeder
  to: "PNL-AIR-3F \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0105
  from: Local panelboard / EE-supplied feeder
  to: "PNL-AIR-BSMT \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0106
  from: Local panelboard / EE-supplied feeder
  to: "PNL-AIR-GF \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0107
  from: Local panelboard / EE-supplied feeder
  to: "PNL-AIR-ROOF \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 35
  length_method: typical_range:panel_power_feed_remote
  length_basis: Remote feeder run including riser segment + horizontal corridor.
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 35 m (typical_range:panel_power_feed_remote)
- id: P0108
  from: Local panelboard / EE-supplied feeder
  to: "PNL-BLR-LG \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0109
  from: Local panelboard / EE-supplied feeder
  to: "PNL-CASINO-GF \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0110
  from: Local panelboard / EE-supplied feeder
  to: "PNL-CH-PLANT-2F \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0111
  from: Local panelboard / EE-supplied feeder
  to: "PNL-CT-ROOF \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 35
  length_method: typical_range:panel_power_feed_remote
  length_basis: Remote feeder run including riser segment + horizontal corridor.
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 35 m (typical_range:panel_power_feed_remote)
- id: P0112
  from: Local panelboard / EE-supplied feeder
  to: "PNL-PL-LG \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
- id: P0113
  from: Local panelboard / EE-supplied feeder
  to: "PNL-PM-LG \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed_local
  length_basis: "Typical local feeder: panel to electrical panelboard within the same plant room or BOH zone \u2014 12\u201322 m measured against EE-03/06/09/12 panel-to-panelboard distances."
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)