# A1 — Consolidated I/O List (Kingsford Hotel Bacolod)
# Generated by _scripts/build-a1.py — re-run after equipment table changes.
#
metadata:
  project: Kingsford Hotel Bacolod — BMS (AB-Run-2)
  date: '2026-04-28'
  source_inputs:
  - 00-customer-inputs/BMS Points list (TUEC).pdf — sheets BMS-01 (Plant + Boilers + Vent), BMS-02 (Casino + Hotel/Boutique), BMS-03 (Control diagrams)
  - 00-customer-inputs/MC Standards - ME Points list.pdf
  - 00-customer-inputs/MC Standards - PL Points list.pdf
  generated_by: _scripts/build-a1.py (project-specific helper, Principle B)
  assumptions_applied:
  - A-002
  - A-003
  - A-006
  - A-016
  - A-017
  - A-018
  status: draft
summary:
  total_points: 474
  total_instances: 59
  by_type:
    DI: 176
    AI: 137
    HLI: 79
    AO: 56
    DO: 14
    Network: 12
  by_panel:
    PNL-CH-PLANT-2F: 107
    PNL-AIR-2F: 75
    PNL-AIR-ROOF: 70
    PNL-CASINO-GF: 50
    PNL-AIR-GF: 39
    PNL-BLR-LG: 37
    PNL-CT-ROOF: 27
    PNL-PL-LG: 23
    PNL-AIR-3F: 20
    PNL-AIR-BSMT: 18
    PNL-PM-LG: 8
  by_co:
    Equipment Supplier: 253
    BMS Contractor: 165
    ME Contractor: 56
io_list:
- id: P0001
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Entering Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0002
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Leaving Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0003
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Entering Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0004
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Leaving Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0005
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Chilled Water Return Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0006
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Chilled Water Supply Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0007
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Condenser Water Supply Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0008
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: CHW Isolation Motorized Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0009
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: COW Isolation Motorized Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0010
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Chiller Native — comprehensive package data (HLI)
  type: Network
  field_device: Chiller Native BACnet IP
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0011
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Chiller Compressor Pump On/Off Status
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0012
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Chiller Compressor HOA Status
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0013
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Chiller Compressor Trip Alarm
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0014
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Motor Load Current
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0015
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Motor Consumption (kW/BTU)
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0016
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Winding Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0017
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Oil Pump Status
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0018
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Oil Pump Trip
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0019
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Oil Sump Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0020
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Oil Sump Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0021
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Evaporator Refrigerant Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0022
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Evaporator Refrigerant Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0023
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Evaporator Approach Δ Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0024
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Evaporator Approach Δ Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0025
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Condenser Refrigerant Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0026
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Condenser Refrigerant Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0027
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Condenser Approach Δ Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0028
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2F Chiller Plant Room
  point_description: Condenser Approach Δ Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 (Chillers @ 2nd Level) + MC-ME
  notes: ''
- id: P0029
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Entering Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0030
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Leaving Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0031
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Entering Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0032
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Leaving Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0033
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Chilled Water Return Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0034
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Chilled Water Supply Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0035
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Condenser Water Supply Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0036
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: CHW Isolation Motorized Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0037
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: COW Isolation Motorized Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0038
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Chiller Native — comprehensive package data (HLI)
  type: Network
  field_device: Chiller Native BACnet IP
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0039
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Chiller Compressor Pump On/Off Status
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0040
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Chiller Compressor HOA Status
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0041
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Chiller Compressor Trip Alarm
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0042
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Motor Load Current
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0043
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Motor Consumption (kW/BTU)
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0044
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Winding Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0045
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Oil Pump Status
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0046
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Oil Pump Trip
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0047
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Oil Sump Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0048
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Oil Sump Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0049
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Evaporator Refrigerant Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0050
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Evaporator Refrigerant Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0051
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Evaporator Approach Δ Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0052
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Evaporator Approach Δ Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0053
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Condenser Refrigerant Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0054
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Condenser Refrigerant Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0055
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Condenser Approach Δ Temperature
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0056
  system: Chilled Water Plant
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2F Chiller Plant Room
  point_description: Condenser Approach Δ Pressure
  type: HLI
  field_device: Chiller Native
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0057
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: CHW Supply Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0058
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0059
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: HOA Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0060
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: VFD Speed Feedback
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0061
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: VFD Speed Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0062
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0063
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1
  location: 2F Chiller Plant Room
  point_description: Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level)
  notes: ''
- id: P0064
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: CHW Supply Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0065
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0066
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: HOA Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0067
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: VFD Speed Feedback
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0068
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: VFD Speed Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0069
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0070
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-2
  location: 2F Chiller Plant Room
  point_description: Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0071
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: CHW Supply Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0072
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0073
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: HOA Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0074
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: VFD Speed Feedback
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0075
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: VFD Speed Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0076
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0077
  system: Chilled Water Plant
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-3
  location: 2F Chiller Plant Room
  point_description: Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0078
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2F Chiller Plant Room
  point_description: On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0079
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2F Chiller Plant Room
  point_description: HOA Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0080
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2F Chiller Plant Room
  point_description: Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0081
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2F Chiller Plant Room
  point_description: Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0082
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2F Chiller Plant Room
  point_description: On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0083
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2F Chiller Plant Room
  point_description: HOA Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0084
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2F Chiller Plant Room
  point_description: Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0085
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2F Chiller Plant Room
  point_description: Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0086
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2F Chiller Plant Room
  point_description: On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0087
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2F Chiller Plant Room
  point_description: HOA Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0088
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2F Chiller Plant Room
  point_description: Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0089
  system: Condenser Water Loop
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2F Chiller Plant Room
  point_description: Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0090
  system: Chilled Water Plant
  equipment_class: CHW Supply Main Header
  equipment_instance: CHW-SUP-HDR
  location: 2F Chiller Plant Room
  point_description: Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0091
  system: Chilled Water Plant
  equipment_class: CHW Supply Main Header
  equipment_instance: CHW-SUP-HDR
  location: 2F Chiller Plant Room
  point_description: Header Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0092
  system: Chilled Water Plant
  equipment_class: CHW Return Main Header
  equipment_instance: CHW-RET-HDR
  location: 2F Chiller Plant Room
  point_description: Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0093
  system: Chilled Water Plant
  equipment_class: CHW Return Main Header
  equipment_instance: CHW-RET-HDR
  location: 2F Chiller Plant Room
  point_description: Header Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME
  notes: ''
- id: P0094
  system: Chilled Water Plant
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYP
  location: 2F Chiller Plant Room
  point_description: Differential Pressure
  type: AI
  field_device: Diff. Pressure Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (CHW Main Header Supply & Return)
  notes: ''
- id: P0095
  system: Chilled Water Plant
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYP
  location: 2F Chiller Plant Room
  point_description: Differential Temperature
  type: AI
  field_device: Diff. Temp Sensor
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (CHW Main Header Supply & Return)
  notes: ''
- id: P0096
  system: Chilled Water Plant
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYP
  location: 2F Chiller Plant Room
  point_description: CHW Bypass Isolation Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (CHW Main Header Supply & Return)
  notes: ''
- id: P0097
  system: Chilled Water Plant
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYP
  location: 2F Chiller Plant Room
  point_description: CHW Bypass Isolation Valve Command
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01 + MC-ME (CHW Main Header Supply & Return)
  notes: ''
- id: P0098
  system: Condenser Water Loop
  equipment_class: Condenser Water Header
  equipment_instance: CW-HDR
  location: Roofdeck Cooling Tower
  point_description: Condenser Water Supply Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0099
  system: Condenser Water Loop
  equipment_class: Condenser Water Header
  equipment_instance: CW-HDR
  location: Roofdeck Cooling Tower
  point_description: Condenser Water Return Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0100
  system: Chilled Water Plant
  equipment_class: BTU Meter
  equipment_instance: BTU-CHW-MAIN
  location: 2F Chiller Plant Room
  point_description: BTU Meter HLI
  type: Network
  field_device: Modbus BTU Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01
  notes: ''
- id: P0101
  system: Chilled Water Plant
  equipment_class: BTU Meter
  equipment_instance: BTU-CHW-MAIN
  location: 2F Chiller Plant Room
  point_description: Energy (kWh/BTU)
  type: HLI
  field_device: Modbus BTU Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01
  notes: ''
- id: P0102
  system: Chilled Water Plant
  equipment_class: BTU Meter
  equipment_instance: BTU-CHW-MAIN
  location: 2F Chiller Plant Room
  point_description: Flow
  type: HLI
  field_device: Modbus BTU Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01
  notes: ''
- id: P0103
  system: Chilled Water Plant
  equipment_class: BTU Meter
  equipment_instance: BTU-CHW-MAIN
  location: 2F Chiller Plant Room
  point_description: Supply T
  type: HLI
  field_device: Modbus BTU Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01
  notes: ''
- id: P0104
  system: Chilled Water Plant
  equipment_class: BTU Meter
  equipment_instance: BTU-CHW-MAIN
  location: 2F Chiller Plant Room
  point_description: Return T
  type: HLI
  field_device: Modbus BTU Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: BMS-01
  notes: ''
- id: P0105
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0106
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Fan Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0107
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Fan Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0108
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Basin Level Low Alarm
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0109
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Basin Level High Alarm
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0110
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0111
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck Cooling Tower
  point_description: Motorized Blowdown Valve Command
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (Cooling Towers @ Roofdeck)
  notes: ''
- id: P0112
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0113
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Fan Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0114
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Fan Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0115
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Basin Level Low Alarm
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0116
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Basin Level High Alarm
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0117
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0118
  system: Condenser Water Loop
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck Cooling Tower
  point_description: Motorized Blowdown Valve Command
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME
  notes: ''
- id: P0119
  system: Condenser Water Loop
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck Cooling Tower
  point_description: Outside Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (basin level + OA T/RH + COW headers)
  notes: ''
- id: P0120
  system: Condenser Water Loop
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck Cooling Tower
  point_description: Outside Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (basin level + OA T/RH + COW headers)
  notes: ''
- id: P0121
  system: Condenser Water Loop
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck Cooling Tower
  point_description: CW Return Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (basin level + OA T/RH + COW headers)
  notes: ''
- id: P0122
  system: Condenser Water Loop
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck Cooling Tower
  point_description: CW Supply Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (basin level + OA T/RH + COW headers)
  notes: ''
- id: P0123
  system: Condenser Water Loop
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck Cooling Tower
  point_description: Blowdown pH/Conductivity
  type: AI
  field_device: pH Sensor / Conductivity Sensor
  c_o: ME Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (basin level + OA T/RH + COW headers)
  notes: ''
- id: P0124
  system: Condenser Water Loop
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck Cooling Tower
  point_description: COW Isolation Motorized Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CT-ROOF
  source: BMS-01 + MC-ME (basin level + OA T/RH + COW headers)
  notes: ''
- id: P0125
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0126
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0127
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0128
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0129
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Indoor Mixed Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0130
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0131
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Indoor Exhaust Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0132
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Indoor Exhaust Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0133
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0134
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0135
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Recovery Wheel Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0136
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Recovery Wheel Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0137
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Supply Fan Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0138
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Supply Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0139
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Supply Fan Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0140
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Supply Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0141
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Supply Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0142
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Exhaust Fan Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0143
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Exhaust Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0144
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Exhaust Fan Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0145
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Exhaust Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0146
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: Exhaust Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0147
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: CHWS Coil Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0148
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roofdeck DOAS
  point_description: CHWS Coil Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1)
  notes: ''
- id: P0149
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0150
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0151
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0152
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0153
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Indoor Mixed Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0154
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0155
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Indoor Exhaust Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0156
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Indoor Exhaust Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0157
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0158
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0159
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Recovery Wheel Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0160
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Recovery Wheel Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0161
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Supply Fan Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0162
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Supply Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0163
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Supply Fan Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0164
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Supply Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0165
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Supply Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0166
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Exhaust Fan Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0167
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Exhaust Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0168
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Exhaust Fan Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0169
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Exhaust Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0170
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: Exhaust Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0171
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: CHWS Coil Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0172
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roofdeck DOAS
  point_description: CHWS Coil Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (DOAS @ Roofdeck RD2)
  notes: ''
- id: P0173
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Outdoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0174
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Outdoor Supply Air Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0175
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Outdoor Supply Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0176
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0177
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Indoor Mixed Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0178
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0179
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Indoor Exhaust Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0180
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Indoor Exhaust Air Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0181
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0182
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0183
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Recovery Wheel Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0184
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Recovery Wheel Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0185
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Supply Fan Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0186
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Supply Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0187
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Supply Fan Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0188
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Supply Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0189
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Supply Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0190
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Exhaust Fan Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0191
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Exhaust Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0192
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Exhaust Fan Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0193
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Exhaust Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0194
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: Exhaust Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0195
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: CHWS Coil Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0196
  system: Ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F Common Public
  point_description: CHWS Coil Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (DOAS @ 2nd Level common/public)
  notes: ''
- id: P0197
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0198
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Outdoor Supply Air Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0199
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0200
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0201
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0202
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0203
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0204
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0205
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0206
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0207
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: CHWS Coil Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0208
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-ROOF
  location: Roofdeck DOAS
  point_description: CHWS Coil Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-ROOF
  source: MC-ME (PAHU @ Roofdeck)
  notes: ''
- id: P0209
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Outdoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0210
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Outdoor Supply Air Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0211
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0212
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0213
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0214
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0215
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0216
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0217
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0218
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0219
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: CHWS Coil Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0220
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-2F
  location: 2F Common Public
  point_description: CHWS Coil Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (PAHU @ 2nd Level)
  notes: ''
- id: P0221
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Outdoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0222
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Outdoor Supply Air Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0223
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0224
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0225
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0226
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0227
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0228
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0229
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0230
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0231
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: CHWS Coil Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0232
  system: Ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-BSMT
  location: Basement BOH
  point_description: CHWS Coil Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-BSMT
  source: MC-ME (PAHU @ Basement)
  notes: ''
- id: P0233
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0234
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0235
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0236
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Indoor Return Air CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0237
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0238
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0239
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Return Air Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0240
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Return Air Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0241
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0242
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0243
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0244
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0245
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: CHWS Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0246
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-A
  location: 2F Common Public
  point_description: CHWS Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME (AHU @ 2nd Level) + BMS-02
  notes: ''
- id: P0247
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0248
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0249
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0250
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Indoor Return Air CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0251
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0252
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0253
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Return Air Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0254
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Return Air Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0255
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0256
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0257
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0258
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0259
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: CHWS Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0260
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-B
  location: 2F Common Public
  point_description: CHWS Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-2F
  source: MC-ME + BMS-02
  notes: ''
- id: P0261
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0262
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0263
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0264
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Indoor Return Air CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0265
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0266
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0267
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Return Air Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0268
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Return Air Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0269
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0270
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0271
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0272
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0273
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: CHWS Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0274
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-LOB
  location: Ground Floor Lobby
  point_description: CHWS Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0275
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0276
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0277
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0278
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Indoor Return Air CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0279
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0280
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0281
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Return Air Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0282
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Return Air Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0283
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0284
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0285
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0286
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0287
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: CHWS Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0288
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-REST
  location: Ground Floor Restaurant
  point_description: CHWS Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-GF
  source: MC-ME (AHU @ GF)
  notes: ''
- id: P0289
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0290
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0291
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Indoor Return Air CO/CO2
  type: AI
  field_device: CO/CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0292
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: OA Damper Position Feedback
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0293
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: OA Damper Modulating Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0294
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Return Damper Position Feedback
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0295
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Return Damper Modulating Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0296
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0297
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0298
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0299
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0300
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: CHWS Modulating Valve Position Feedback
  type: AI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0301
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: CHWS Modulating Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0302
  system: Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-GF-CASINO
  location: Ground Floor Casino Lobby
  point_description: Ozone VOC Reading
  type: AI
  field_device: VOC Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS) + MC-ME
  notes: ''
- id: P0303
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0304
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0305
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Indoor Return Air CO/CO2
  type: AI
  field_device: CO/CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0306
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: OA Damper Position Feedback
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0307
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: OA Damper Modulating Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0308
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Return Damper Position Feedback
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0309
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Return Damper Modulating Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0310
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0311
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0312
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0313
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0314
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: CHWS Modulating Valve Position Feedback
  type: AI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0315
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: CHWS Modulating Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0316
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-1
  location: Ground Floor Casino
  point_description: Ozone VOC Reading
  type: AI
  field_device: VOC Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02 (Casino BMS Equipment I/O Tabulation)
  notes: ''
- id: P0317
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0318
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0319
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Indoor Return Air CO/CO2
  type: AI
  field_device: CO/CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0320
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: OA Damper Position Feedback
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0321
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: OA Damper Modulating Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0322
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Return Damper Position Feedback
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0323
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Return Damper Modulating Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0324
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0325
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0326
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0327
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0328
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: CHWS Modulating Valve Position Feedback
  type: AI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0329
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: CHWS Modulating Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0330
  system: Casino Air Conditioning
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-CASINO-2
  location: Ground Floor Casino
  point_description: Ozone VOC Reading
  type: AI
  field_device: VOC Sensor
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0331
  system: Casino Air Conditioning
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: OZ-CASINO-1
  location: Ground Floor Casino
  point_description: Ozone Generator Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0332
  system: Casino Air Conditioning
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: OZ-CASINO-1
  location: Ground Floor Casino
  point_description: Ozone Generator Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0333
  system: Casino Air Conditioning
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: OZ-CASINO-1
  location: Ground Floor Casino
  point_description: Ozone Generator Start/Stop
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-CASINO-GF
  source: BMS-02
  notes: ''
- id: P0334
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Indoor Supply Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0335
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Indoor Mixed Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0336
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Indoor Return Air Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0337
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Indoor Return Air CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0338
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: OA Damper Status
  type: DI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0339
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: OA Damper Command
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0340
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Return Air Damper Status
  type: DI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0341
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Return Air Damper Command
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0342
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0343
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0344
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Fan VFD Speed
  type: AI
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0345
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: Fan VFD Command
  type: AO
  field_device: VFD
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0346
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: CHWS Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0347
  system: Air Conditioning
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-3F-AM
  location: 3F Amenity
  point_description: CHWS Valve Command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity)
  notes: ''
- id: P0348
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-BSMT
  location: Basement BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: BMS-01 (Basement toilet exhaust)
  notes: ''
- id: P0349
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-BSMT
  location: Basement BOH
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: BMS-01 (Basement toilet exhaust)
  notes: ''
- id: P0350
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-BSMT
  location: Basement BOH
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: BMS-01 (Basement toilet exhaust)
  notes: ''
- id: P0351
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-BSMT
  location: Basement BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: BMS-01
  notes: ''
- id: P0352
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-BSMT
  location: Basement BOH
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: BMS-01
  notes: ''
- id: P0353
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-BSMT
  location: Basement BOH
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-BSMT
  source: BMS-01
  notes: ''
- id: P0354
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-GF
  location: Ground Floor Lobby
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (GF main lobby toilet exhaust)
  notes: ''
- id: P0355
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-GF
  location: Ground Floor Lobby
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (GF main lobby toilet exhaust)
  notes: ''
- id: P0356
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-GF
  location: Ground Floor Lobby
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME (GF main lobby toilet exhaust)
  notes: ''
- id: P0357
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-GF
  location: Ground Floor Lobby
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME
  notes: ''
- id: P0358
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-GF
  location: Ground Floor Lobby
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME
  notes: ''
- id: P0359
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-GF
  location: Ground Floor Lobby
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-GF
  source: MC-ME
  notes: ''
- id: P0360
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-2F
  location: 2F Common Public
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (2nd Floor toilet exhaust)
  notes: ''
- id: P0361
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-2F
  location: 2F Common Public
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (2nd Floor toilet exhaust)
  notes: ''
- id: P0362
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-2F
  location: 2F Common Public
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME (2nd Floor toilet exhaust)
  notes: ''
- id: P0363
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-2F
  location: 2F Common Public
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME
  notes: ''
- id: P0364
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-2F
  location: 2F Common Public
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME
  notes: ''
- id: P0365
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-2F
  location: 2F Common Public
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-2F
  source: MC-ME
  notes: ''
- id: P0366
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-3F
  location: 3F Amenity
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity toilet exhaust)
  notes: ''
- id: P0367
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-3F
  location: 3F Amenity
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity toilet exhaust)
  notes: ''
- id: P0368
  system: Exhaust
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: EAS-TOILET-3F
  location: 3F Amenity
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME (3F amenity toilet exhaust)
  notes: ''
- id: P0369
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-3F
  location: 3F Amenity
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME
  notes: ''
- id: P0370
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-3F
  location: 3F Amenity
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME
  notes: ''
- id: P0371
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-3F
  location: 3F Amenity
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-3F
  source: MC-ME
  notes: ''
- id: P0372
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-ROOF
  location: Roofdeck DOAS
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (Roofdeck general exhaust)
  notes: ''
- id: P0373
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-ROOF
  location: Roofdeck DOAS
  point_description: Fan Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (Roofdeck general exhaust)
  notes: ''
- id: P0374
  system: Exhaust
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GEN-ROOF
  location: Roofdeck DOAS
  point_description: Fan Motor Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-ME (Roofdeck general exhaust)
  notes: ''
- id: P0375
  system: Hot Water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CALOR-LG
  location: Lower Ground Calorifier Room
  point_description: Tank Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: MC-PL (Calorifiers @ Lower Ground)
  notes: ''
- id: P0376
  system: Hot Water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CALOR-ROOF
  location: Roofdeck DOAS
  point_description: Tank Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-AIR-ROOF
  source: MC-PL (Calorifiers @ Roofdeck)
  notes: ''
- id: P0377
  system: Hot Water
  equipment_class: Hot Water Header Set
  equipment_instance: HW-HEADERS-LG
  location: Lower Ground Calorifier Room
  point_description: HW Supply Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: MC-PL (Supply & Return Headers @ Lower Ground)
  notes: ''
- id: P0378
  system: Hot Water
  equipment_class: Hot Water Header Set
  equipment_instance: HW-HEADERS-LG
  location: Lower Ground Calorifier Room
  point_description: Make-up Cold Water Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: MC-PL (Supply & Return Headers @ Lower Ground)
  notes: ''
- id: P0379
  system: Hot Water
  equipment_class: Hot Water Header Set
  equipment_instance: HW-HEADERS-LG
  location: Lower Ground Calorifier Room
  point_description: HW Return Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: MC-PL (Supply & Return Headers @ Lower Ground)
  notes: ''
- id: P0380
  system: Hot Water
  equipment_class: Heat Pump
  equipment_instance: HP-LG-1
  location: Lower Ground Calorifier Room
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL (Heat Pump @ Lower Ground)
  notes: ''
- id: P0381
  system: Hot Water
  equipment_class: Heat Pump
  equipment_instance: HP-LG-1
  location: Lower Ground Calorifier Room
  point_description: Pump Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL (Heat Pump @ Lower Ground)
  notes: ''
- id: P0382
  system: Hot Water
  equipment_class: Heat Pump
  equipment_instance: HP-LG-1
  location: Lower Ground Calorifier Room
  point_description: Pump Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL (Heat Pump @ Lower Ground)
  notes: ''
- id: P0383
  system: Hot Water
  equipment_class: Heat Pump
  equipment_instance: HP-ROOF-1
  location: Roofdeck DOAS
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-PL (Heat Pump @ Roofdeck)
  notes: ''
- id: P0384
  system: Hot Water
  equipment_class: Heat Pump
  equipment_instance: HP-ROOF-1
  location: Roofdeck DOAS
  point_description: Pump Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-PL (Heat Pump @ Roofdeck)
  notes: ''
- id: P0385
  system: Hot Water
  equipment_class: Heat Pump
  equipment_instance: HP-ROOF-1
  location: Roofdeck DOAS
  point_description: Pump Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-PL (Heat Pump @ Roofdeck)
  notes: ''
- id: P0386
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-LG-1
  location: Lower Ground Calorifier Room
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL (Circulating Pumps @ Lower Ground)
  notes: ''
- id: P0387
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-LG-1
  location: Lower Ground Calorifier Room
  point_description: Pump Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL (Circulating Pumps @ Lower Ground)
  notes: ''
- id: P0388
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-LG-1
  location: Lower Ground Calorifier Room
  point_description: Pump Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL (Circulating Pumps @ Lower Ground)
  notes: ''
- id: P0389
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-LG-2
  location: Lower Ground Calorifier Room
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL
  notes: ''
- id: P0390
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-LG-2
  location: Lower Ground Calorifier Room
  point_description: Pump Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL
  notes: ''
- id: P0391
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-LG-2
  location: Lower Ground Calorifier Room
  point_description: Pump Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-PL-LG
  source: MC-PL
  notes: ''
- id: P0392
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-ROOF-1
  location: Roofdeck DOAS
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-PL (Roofdeck circulating pumps)
  notes: ''
- id: P0393
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-ROOF-1
  location: Roofdeck DOAS
  point_description: Pump Motor HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-PL (Roofdeck circulating pumps)
  notes: ''
- id: P0394
  system: Hot Water
  equipment_class: Recirculating Pump
  equipment_instance: HW-PUMP-ROOF-1
  location: Roofdeck DOAS
  point_description: Pump Trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-AIR-ROOF
  source: MC-PL (Roofdeck circulating pumps)
  notes: ''
- id: P0395
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Supply Steam Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0396
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Feedwater Supply Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0397
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Fluegas Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0398
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Fluegas Oxygen Level
  type: AI
  field_device: Oxygen Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0399
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Boiler Water Low Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0400
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Boiler Water High Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0401
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Burner Power
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0402
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Small Fire Control Signal
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0403
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Big Fire Control Signal
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0404
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Waterfeed Pump Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0405
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Burner Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0406
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Burner Fire Running Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0407
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Blower Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0408
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Fuel Oil Pump Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0409
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0410
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-1
  location: Lower Ground Boiler Room
  point_description: Motorized Blowdown Valve Command
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 (Boilers @ Lower Ground) + MC-ME
  notes: ''
- id: P0411
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Supply Steam Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0412
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Feedwater Supply Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0413
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Fluegas Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0414
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Fluegas Oxygen Level
  type: AI
  field_device: Oxygen Sensor
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0415
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Boiler Water Low Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0416
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Boiler Water High Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0417
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Burner Power
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0418
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Small Fire Control Signal
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0419
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Big Fire Control Signal
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0420
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Waterfeed Pump Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0421
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Burner Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0422
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Burner Fire Running Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0423
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Blower Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0424
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Fuel Oil Pump Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0425
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0426
  system: Boiler
  equipment_class: Steam Boiler
  equipment_instance: BLR-2
  location: Lower Ground Boiler Room
  point_description: Motorized Blowdown Valve Command
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: BMS-01 + MC-ME
  notes: ''
- id: P0427
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0428
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0429
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0430
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0431
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Reactive Power kVAR
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0432
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Power Factor
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0433
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0434
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN-LG
  location: Lower Ground Main Switchgear
  point_description: Frequency Hz
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PM-LG
  source: EE-21 (main service entry) + BMS-01 spec
  notes: ''
- id: P0435
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER
  location: 2F Chiller Plant Room
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: EE-21 + BMS-01 (chiller feeders)
  notes: ''
- id: P0436
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER
  location: 2F Chiller Plant Room
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: EE-21 + BMS-01 (chiller feeders)
  notes: ''
- id: P0437
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER
  location: 2F Chiller Plant Room
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: EE-21 + BMS-01 (chiller feeders)
  notes: ''
- id: P0438
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER
  location: 2F Chiller Plant Room
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: EE-21 + BMS-01 (chiller feeders)
  notes: ''
- id: P0439
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER
  location: 2F Chiller Plant Room
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CH-PLANT-2F
  source: EE-21 + BMS-01 (chiller feeders)
  notes: ''
- id: P0440
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-COOLING
  location: Roofdeck Cooling Tower
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: EE-22 + BMS-01
  notes: ''
- id: P0441
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-COOLING
  location: Roofdeck Cooling Tower
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: EE-22 + BMS-01
  notes: ''
- id: P0442
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-COOLING
  location: Roofdeck Cooling Tower
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: EE-22 + BMS-01
  notes: ''
- id: P0443
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-COOLING
  location: Roofdeck Cooling Tower
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: EE-22 + BMS-01
  notes: ''
- id: P0444
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-COOLING
  location: Roofdeck Cooling Tower
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CT-ROOF
  source: EE-22 + BMS-01
  notes: ''
- id: P0445
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-2F
  location: 2F Common Public
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: EE-22
  notes: ''
- id: P0446
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-2F
  location: 2F Common Public
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: EE-22
  notes: ''
- id: P0447
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-2F
  location: 2F Common Public
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: EE-22
  notes: ''
- id: P0448
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-2F
  location: 2F Common Public
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: EE-22
  notes: ''
- id: P0449
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-2F
  location: 2F Common Public
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-2F
  source: EE-22
  notes: ''
- id: P0450
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-GF
  location: Ground Floor Lobby
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: EE-22
  notes: ''
- id: P0451
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-GF
  location: Ground Floor Lobby
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: EE-22
  notes: ''
- id: P0452
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-GF
  location: Ground Floor Lobby
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: EE-22
  notes: ''
- id: P0453
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-GF
  location: Ground Floor Lobby
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: EE-22
  notes: ''
- id: P0454
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-AIR-GF
  location: Ground Floor Lobby
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-AIR-GF
  source: EE-22
  notes: ''
- id: P0455
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CASINO
  location: Ground Floor Casino
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: EE-22 (Casino feeder)
  notes: ''
- id: P0456
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CASINO
  location: Ground Floor Casino
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: EE-22 (Casino feeder)
  notes: ''
- id: P0457
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CASINO
  location: Ground Floor Casino
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: EE-22 (Casino feeder)
  notes: ''
- id: P0458
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CASINO
  location: Ground Floor Casino
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: EE-22 (Casino feeder)
  notes: ''
- id: P0459
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CASINO
  location: Ground Floor Casino
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-CASINO-GF
  source: EE-22 (Casino feeder)
  notes: ''
- id: P0460
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-BOILER
  location: Lower Ground Boiler Room
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: EE-23 (boiler feeder)
  notes: ''
- id: P0461
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-BOILER
  location: Lower Ground Boiler Room
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: EE-23 (boiler feeder)
  notes: ''
- id: P0462
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-BOILER
  location: Lower Ground Boiler Room
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: EE-23 (boiler feeder)
  notes: ''
- id: P0463
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-BOILER
  location: Lower Ground Boiler Room
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: EE-23 (boiler feeder)
  notes: ''
- id: P0464
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-BOILER
  location: Lower Ground Boiler Room
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-BLR-LG
  source: EE-23 (boiler feeder)
  notes: ''
- id: P0465
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-PLUMB
  location: Lower Ground Calorifier Room
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (plumbing pumproom feeder)
  notes: ''
- id: P0466
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-PLUMB
  location: Lower Ground Calorifier Room
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (plumbing pumproom feeder)
  notes: ''
- id: P0467
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-PLUMB
  location: Lower Ground Calorifier Room
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (plumbing pumproom feeder)
  notes: ''
- id: P0468
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-PLUMB
  location: Lower Ground Calorifier Room
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (plumbing pumproom feeder)
  notes: ''
- id: P0469
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-PLUMB
  location: Lower Ground Calorifier Room
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (plumbing pumproom feeder)
  notes: ''
- id: P0470
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-FIREPMP
  location: Lower Ground Boiler Room
  point_description: Power Meter Modbus Network
  type: Network
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (fire pump feeder per CB#8 — single-feeder scheme)
  notes: ''
- id: P0471
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-FIREPMP
  location: Lower Ground Boiler Room
  point_description: Voltage L-L (3-phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (fire pump feeder per CB#8 — single-feeder scheme)
  notes: ''
- id: P0472
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-FIREPMP
  location: Lower Ground Boiler Room
  point_description: Current per phase
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (fire pump feeder per CB#8 — single-feeder scheme)
  notes: ''
- id: P0473
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-FIREPMP
  location: Lower Ground Boiler Room
  point_description: Real Power kW
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (fire pump feeder per CB#8 — single-feeder scheme)
  notes: ''
- id: P0474
  system: Power Monitoring
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-FIREPMP
  location: Lower Ground Boiler Room
  point_description: Energy kWh
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  panel: PNL-PL-LG
  source: EE-23 (fire pump feeder per CB#8 — single-feeder scheme)
  notes: ''