# B3 — Commissioning Point Inventory
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS Rehabilitation (A/B run)"
  generated_from: A1-io-list.yaml + A2-equipment-takeoff.yaml
  generator: _playbook/tools/generate-b1-b3-programming-and-commissioning.py
  rates:
    hrs_per_p2p_point: 0.15
    hrs_per_functional_test: 1.5
    hrs_per_integrated_test: 4.0
summary:
  p2p_points: 629
  functional_tests: 125
  integrated_tests: 8
  total_test_items: 762
tc_hours:
  point_to_point: 94.3
  functional_per_equipment: 187.5
  integrated_sequences: 32.0
  total_tc_hours: 313.8
  person_days_at_8hr: 39.2
p2p_breakdown_by_panel:
  FCP-2F: 234
  FCP-RD: 113
  FCP-3F: 81
  FCP-BSMT: 72
  MCP-PLANT: 66
  FCP-GF: 63
functional_test_inventory:
- equipment: AHU-1.1
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor
- equipment: AHU-1.2
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor
- equipment: AHU-1.3
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor
- equipment: AHU-2M.1
  equipment_class: AHU (Modulating CHW-served)
  location: 2nd Floor (Casino)
- equipment: AHU-2M.2
  equipment_class: AHU (Modulating CHW-served)
  location: 2nd Floor (Casino)
- equipment: AHU-B.1
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: AHU-B.2
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: AHU-B.3
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: AHU-EL
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: AHU-FR2
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: AHU-FR3
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: AHU-PF
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor
- equipment: ATS-1
  equipment_class: Multifunction Power Meter (Main)
  location: Basement (Genset)
- equipment: BLR-1
  equipment_class: Steam Boiler
  location: Lower Ground
- equipment: BLR-2
  equipment_class: Steam Boiler
  location: Lower Ground
- equipment: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Floor (Plant Room)
- equipment: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Floor (Plant Room)
- equipment: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Floor (Plant Room)
- equipment: CHW-BYPASS
  equipment_class: CHW Bypass Header
  location: 2nd Floor (Plant Room)
- equipment: CHW-HDR-R
  equipment_class: CHW Return Main Header
  location: 2nd Floor (Plant Room)
- equipment: CHW-HDR-S
  equipment_class: CHW Supply Main Header
  location: 2nd Floor (Plant Room)
- equipment: COW-HDR
  equipment_class: Condenser Water Header
  location: Roofdeck
- equipment: CT-1
  equipment_class: Cooling Tower
  location: Roofdeck
- equipment: CT-2
  equipment_class: Cooling Tower
  location: Roofdeck
- equipment: CT-3
  equipment_class: Cooling Tower
  location: Roofdeck
- equipment: CT-COMMON
  equipment_class: Cooling Tower (Common)
  location: Roofdeck
- equipment: DOAS-2M
  equipment_class: DOAS Unit
  location: 2nd Floor (Casino)
- equipment: DOAS-RD.1
  equipment_class: DOAS Unit
  location: Roofdeck
- equipment: DOAS-RD.2
  equipment_class: DOAS Unit
  location: Roofdeck
- equipment: EF-1.2A
  equipment_class: Exhaust Fan (General)
  location: Ground Floor
- equipment: EF-1MR.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor
- equipment: EF-1ST0.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor
- equipment: EF-2.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2.3
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2.4
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2B.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2B.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-3GE.1
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor (Amenity)
- equipment: EF-3GE.2
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor (Amenity)
- equipment: EF-CHR.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-CHR.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-GS.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-GS.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-LPG.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor
- equipment: EF-MRF.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor
- equipment: GEN-1
  equipment_class: Multifunction Power Meter (Main)
  location: Basement (Genset)
- equipment: HP-HZ.1
  equipment_class: Heat Pump
  location: Roofdeck
- equipment: HP-HZ.2
  equipment_class: Heat Pump
  location: Roofdeck
- equipment: HP-HZ.3
  equipment_class: Heat Pump
  location: Roofdeck
- equipment: HP-LZ.1
  equipment_class: Heat Pump
  location: Lower Ground
- equipment: HP-LZ.2
  equipment_class: Heat Pump
  location: Lower Ground
- equipment: HP-LZ.3
  equipment_class: Heat Pump
  location: Lower Ground
- equipment: HW-HDR-HZ
  equipment_class: Hot Water Header Set
  location: Roofdeck
- equipment: HW-HDR-LZ
  equipment_class: Hot Water Header Set
  location: Lower Ground
- equipment: HWT-HZ.1
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roofdeck
- equipment: HWT-HZ.2
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roofdeck
- equipment: HWT-HZ.3
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roofdeck
- equipment: HWT-LZ.1
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground
- equipment: HWT-LZ.2
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground
- equipment: HWT-LZ.3
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground
- equipment: ION-2M.1
  equipment_class: Ozone Generator (UV-light or Corona)
  location: 2nd Floor (Casino)
- equipment: ION-2M.2
  equipment_class: Ozone Generator (UV-light or Corona)
  location: 2nd Floor (Casino)
- equipment: PAHU-0.1
  equipment_class: Precooled Air Handling Unit
  location: Basement
- equipment: PAHU-B1
  equipment_class: Precooled Air Handling Unit
  location: 2nd Floor
- equipment: PAHU-B2
  equipment_class: Precooled Air Handling Unit
  location: 2nd Floor
- equipment: PAHU-B3
  equipment_class: Precooled Air Handling Unit
  location: 2nd Floor
- equipment: PAHU-FR
  equipment_class: Precooled Air Handling Unit
  location: 2nd Floor
- equipment: PAHU-PF
  equipment_class: Precooled Air Handling Unit
  location: 2nd Floor
- equipment: PAHU-RD.1
  equipment_class: Precooled Air Handling Unit
  location: Roofdeck
- equipment: PAHU-RD.2
  equipment_class: Precooled Air Handling Unit
  location: Roofdeck
- equipment: PCHW-1
  equipment_class: Primary CHW Pump
  location: 2nd Floor (Plant Room)
- equipment: PCHW-2
  equipment_class: Primary CHW Pump
  location: 2nd Floor (Plant Room)
- equipment: PCHW-3
  equipment_class: Primary CHW Pump
  location: 2nd Floor (Plant Room)
- equipment: PCHW-S
  equipment_class: Primary CHW Pump (Standby)
  location: 2nd Floor (Plant Room)
- equipment: PCOW-1
  equipment_class: Condenser Water Pump
  location: 2nd Floor (Plant Room)
- equipment: PCOW-2
  equipment_class: Condenser Water Pump
  location: 2nd Floor (Plant Room)
- equipment: PCOW-3
  equipment_class: Condenser Water Pump
  location: 2nd Floor (Plant Room)
- equipment: PM-GEN
  equipment_class: Multifunction Power Meter (Main)
  location: 2nd Floor (Plant Room)
- equipment: PM-MAIN
  equipment_class: Multifunction Power Meter (Main)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-BOILER
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-CHILLER
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-CT
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-FIRE-PUMP
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-MDP-1
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-MDP-2
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: PM-MCC-MDP-3
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor (Plant Room)
- equipment: RP-HZ.1
  equipment_class: Recirculating Pump
  location: Roofdeck
- equipment: RP-HZ.2
  equipment_class: Recirculating Pump
  location: Roofdeck
- equipment: RP-HZ.3
  equipment_class: Recirculating Pump
  location: Roofdeck
- equipment: RP-LZ.1
  equipment_class: Recirculating Pump
  location: Lower Ground
- equipment: RP-LZ.2
  equipment_class: Recirculating Pump
  location: Lower Ground
- equipment: RP-LZ.3
  equipment_class: Recirculating Pump
  location: Lower Ground
- equipment: TEF-1.1
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor
- equipment: TEF-1.2
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor
- equipment: TEF-1.3
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor
- equipment: TEF-1.4
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor
- equipment: TEF-2.1
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor
- equipment: TEF-2.3
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor
- equipment: TEF-2B.3
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor
- equipment: TEF-3A.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Amenity)
- equipment: TEF-3A.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Amenity)
- equipment: TEF-3B.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Amenity)
- equipment: TEF-3C.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Amenity)
- equipment: TEF-3C.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Amenity)
- equipment: TEF-3D.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.10
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.11
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.12
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.13
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.14
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.15
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.16
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.17
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.18
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.19
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.20
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.3
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.4
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.5
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.6
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.7
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.8
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
- equipment: TEF-3D.9
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor (Guestroom)
integrated_test_inventory:
- Chiller plant sequencing (chiller staging + CHW pump + COW pump + cooling tower fan)
- CHW differential pressure control (PCHWP VFD speed via header dP)
- AHU supply-air temperature control (modulating CHW valve loop)
- DOAS demand-controlled ventilation (CO2-based fresh air modulation)
- Hotwater system sequencing (heat pump + recirculating pump + tank temp)
- Boiler firing rate vs. steam pressure
- Cooling tower fan staging vs. condenser water temperature
- Energy savings algorithm verification (max-demand limiting + load shedding)
notes:
- 'P2P = point-to-point verification: every physical I/O calibrated, range-checked, polarity verified, scaled correctly.'
- 'Functional test: per-equipment sequence verification (e.g., does the AHU CHW valve modulate correctly to maintain supply air temp?).'
- 'Integrated test: cross-system sequence (e.g., chiller staging triggers correctly when load increases).'
- "Owner T&C / SAT: separate from this \u2014 handled in proposal as an item under 5.5 in WBS."