# A3 — Cable Schedule
# Generated from A1-io-list.yaml; lengths per A-001
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS Rehabilitation (A/B run)"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a3-cable-schedule.py
  assumptions:
  - 'A-001: 30 m average panel-to-device run; 80 m trunk per floor'
  - Cable conductor count = (points + 2 spare), rounded up to standard 4/6/8/12 sizes
  - Cat6 for all BACnet/IP network drops
  - BACnet MS/TP backbone interconnects all BMS panels (refine after Q-008)
  - 240V single-phase power feed to each BMS panel @ 30 m default length
summary:
  total_field_cable_runs: 198
  total_field_cable_length_m: 5940
  total_trunk_cable_length_m: 660
  total_power_feed_length_m: 180
  grand_total_cable_length_m: 6780
  field_cable_by_type_m:
    "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)": 2940
    "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)": 1380
    "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)": 870
    "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)": 690
    "Modbus shielded twisted-pair, 1pr \xD7 22 AWG (e.g., Belden 9841)": 60
  field_cable_by_panel_m:
    FCP-GF: 18
    FCP-2F: 68
    FCP-BSMT: 20
    MCP-PLANT: 28
    FCP-RD: 37
    FCP-3F: 27
field_cables:
- id: C0001
  from: FCP-GF
  to: AHU-1.1 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0003
  - P0004
  - P0010
  - P0011
  - P0014
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0002
  from: FCP-GF
  to: AHU-1.1 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0006
  - P0007
  - P0012
  - P0013
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0003
  from: FCP-GF
  to: AHU-1.1 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0001
  - P0002
  - P0005
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0004
  from: FCP-GF
  to: AHU-1.2 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0017
  - P0018
  - P0024
  - P0025
  - P0028
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0005
  from: FCP-GF
  to: AHU-1.2 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0020
  - P0021
  - P0026
  - P0027
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0006
  from: FCP-GF
  to: AHU-1.2 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0015
  - P0016
  - P0019
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0007
  from: FCP-GF
  to: AHU-1.3 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0031
  - P0032
  - P0038
  - P0039
  - P0042
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0008
  from: FCP-GF
  to: AHU-1.3 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0034
  - P0035
  - P0040
  - P0041
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0009
  from: FCP-GF
  to: AHU-1.3 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0029
  - P0030
  - P0033
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0010
  from: FCP-2F
  to: AHU-2M.1 (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 10
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 8
  carries_point_ids:
  - P0227
  - P0228
  - P0234
  - P0235
  - P0238
  - '...'
  notes: 8 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0011
  from: FCP-2F
  to: AHU-2M.1 (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0230
  - P0231
  - P0236
  - P0237
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0012
  from: FCP-2F
  to: AHU-2M.1 (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0225
  - P0226
  - P0229
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0013
  from: FCP-2F
  to: AHU-2M.2 (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 10
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 8
  carries_point_ids:
  - P0244
  - P0245
  - P0251
  - P0252
  - P0255
  - '...'
  notes: 8 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0014
  from: FCP-2F
  to: AHU-2M.2 (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0247
  - P0248
  - P0253
  - P0254
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0015
  from: FCP-2F
  to: AHU-2M.2 (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0242
  - P0243
  - P0246
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0016
  from: FCP-2F
  to: AHU-B.1 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0045
  - P0046
  - P0052
  - P0053
  - P0056
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0017
  from: FCP-2F
  to: AHU-B.1 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0048
  - P0049
  - P0054
  - P0055
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0018
  from: FCP-2F
  to: AHU-B.1 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0043
  - P0044
  - P0047
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0019
  from: FCP-2F
  to: AHU-B.2 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0059
  - P0060
  - P0066
  - P0067
  - P0070
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0020
  from: FCP-2F
  to: AHU-B.2 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0062
  - P0063
  - P0068
  - P0069
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0021
  from: FCP-2F
  to: AHU-B.2 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0057
  - P0058
  - P0061
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0022
  from: FCP-2F
  to: AHU-B.3 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0073
  - P0074
  - P0080
  - P0081
  - P0084
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0023
  from: FCP-2F
  to: AHU-B.3 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0076
  - P0077
  - P0082
  - P0083
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0024
  from: FCP-2F
  to: AHU-B.3 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0071
  - P0072
  - P0075
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0025
  from: FCP-2F
  to: AHU-EL (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0101
  - P0102
  - P0108
  - P0109
  - P0112
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0026
  from: FCP-2F
  to: AHU-EL (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0104
  - P0105
  - P0110
  - P0111
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0027
  from: FCP-2F
  to: AHU-EL (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0099
  - P0100
  - P0103
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0028
  from: FCP-2F
  to: AHU-FR2 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0115
  - P0116
  - P0122
  - P0123
  - P0126
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0029
  from: FCP-2F
  to: AHU-FR2 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0118
  - P0119
  - P0124
  - P0125
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0030
  from: FCP-2F
  to: AHU-FR2 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0113
  - P0114
  - P0117
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0031
  from: FCP-2F
  to: AHU-FR3 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0129
  - P0130
  - P0136
  - P0137
  - P0140
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0032
  from: FCP-2F
  to: AHU-FR3 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0132
  - P0133
  - P0138
  - P0139
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0033
  from: FCP-2F
  to: AHU-FR3 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0127
  - P0128
  - P0131
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0034
  from: FCP-2F
  to: AHU-PF (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0087
  - P0088
  - P0094
  - P0095
  - P0098
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0035
  from: FCP-2F
  to: AHU-PF (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0090
  - P0091
  - P0096
  - P0097
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0036
  from: FCP-2F
  to: AHU-PF (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: AC
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0085
  - P0086
  - P0089
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0037
  from: FCP-BSMT
  to: ATS-1 (EE Contractor)
  equipment_class: Multifunction Power Meter (Main)
  system: EE
  location: Basement (Genset)
  cable_type: "Modbus shielded twisted-pair, 1pr \xD7 22 AWG (e.g., Belden 9841)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0761
  - P0762
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0038
  from: FCP-BSMT
  to: BLR-1 (BMS Contractor)
  equipment_class: Steam Boiler
  system: VENT
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 6
  carries_point_ids:
  - P0669
  - P0680
  - P0681
  - P0682
  - P0683
  - '...'
  notes: 6 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0039
  from: FCP-BSMT
  to: BLR-1 (Equipment Supplier)
  equipment_class: Steam Boiler
  system: VENT
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 10
  carries_point_ids:
  - P0670
  - P0671
  - P0672
  - P0673
  - P0674
  - '...'
  notes: 10 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0040
  from: FCP-BSMT
  to: BLR-2 (BMS Contractor)
  equipment_class: Steam Boiler
  system: VENT
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 6
  carries_point_ids:
  - P0685
  - P0696
  - P0697
  - P0698
  - P0699
  - '...'
  notes: 6 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0041
  from: FCP-BSMT
  to: BLR-2 (Equipment Supplier)
  equipment_class: Steam Boiler
  system: VENT
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 10
  carries_point_ids:
  - P0686
  - P0687
  - P0688
  - P0689
  - P0690
  - '...'
  notes: 10 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0042
  from: MCP-PLANT
  to: CH-1 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 7
  carries_point_ids:
  - P0515
  - P0516
  - P0539
  - P0540
  - P0541
  - '...'
  notes: 7 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0043
  from: MCP-PLANT
  to: CH-1 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0517
  - P0518
  - P0537
  - P0538
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0044
  from: MCP-PLANT
  to: CH-2 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 7
  carries_point_ids:
  - P0545
  - P0546
  - P0569
  - P0570
  - P0571
  - '...'
  notes: 7 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0045
  from: MCP-PLANT
  to: CH-2 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0547
  - P0548
  - P0567
  - P0568
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0046
  from: MCP-PLANT
  to: CH-3 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 9
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 7
  carries_point_ids:
  - P0575
  - P0576
  - P0599
  - P0600
  - P0601
  - '...'
  notes: 7 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0047
  from: MCP-PLANT
  to: CH-3 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0577
  - P0578
  - P0597
  - P0598
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0048
  from: MCP-PLANT
  to: CHW-BYPASS (BMS Contractor)
  equipment_class: CHW Bypass Header
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0663
  - P0664
  - P0665
  - P0666
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0049
  from: MCP-PLANT
  to: CHW-HDR-R (BMS Contractor)
  equipment_class: CHW Return Main Header
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0661
  - P0662
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0050
  from: MCP-PLANT
  to: CHW-HDR-S (BMS Contractor)
  equipment_class: CHW Supply Main Header
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0659
  - P0660
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0051
  from: FCP-RD
  to: COW-HDR (BMS Contractor)
  equipment_class: Condenser Water Header
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0667
  - P0668
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0052
  from: FCP-RD
  to: CT-1 (BMS Contractor)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0636
  - P0637
  - P0640
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0053
  from: FCP-RD
  to: CT-1 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0634
  - P0635
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0054
  from: FCP-RD
  to: CT-1 (ME Contractor)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0638
  - P0639
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0055
  from: FCP-RD
  to: CT-2 (BMS Contractor)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0643
  - P0644
  - P0647
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0056
  from: FCP-RD
  to: CT-2 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0641
  - P0642
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0057
  from: FCP-RD
  to: CT-2 (ME Contractor)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0645
  - P0646
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0058
  from: FCP-RD
  to: CT-3 (BMS Contractor)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0650
  - P0651
  - P0654
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0059
  from: FCP-RD
  to: CT-3 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0648
  - P0649
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0060
  from: FCP-RD
  to: CT-3 (ME Contractor)
  equipment_class: Cooling Tower
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0652
  - P0653
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0061
  from: FCP-RD
  to: CT-COMMON (BMS Contractor)
  equipment_class: Cooling Tower (Common)
  system: AC
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0655
  - P0656
  - P0657
  - P0658
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0062
  from: FCP-2F
  to: DOAS-2M (BMS Contractor)
  equipment_class: DOAS Unit
  system: VENT
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 6
  carries_point_ids:
  - P0259
  - P0260
  - P0261
  - P0275
  - P0276
  - '...'
  notes: 6 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0063
  from: FCP-2F
  to: DOAS-2M (Equipment Supplier)
  equipment_class: DOAS Unit
  system: VENT
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 10
  carries_point_ids:
  - P0264
  - P0265
  - P0266
  - P0267
  - P0268
  - '...'
  notes: 10 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0064
  from: FCP-2F
  to: DOAS-2M (ME Contractor)
  equipment_class: DOAS Unit
  system: VENT
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0262
  - P0263
  - P0273
  - P0274
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0065
  from: FCP-RD
  to: DOAS-RD.1 (BMS Contractor)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 6
  carries_point_ids:
  - P0284
  - P0285
  - P0286
  - P0300
  - P0301
  - '...'
  notes: 6 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0066
  from: FCP-RD
  to: DOAS-RD.1 (Equipment Supplier)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 10
  carries_point_ids:
  - P0289
  - P0290
  - P0291
  - P0292
  - P0293
  - '...'
  notes: 10 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0067
  from: FCP-RD
  to: DOAS-RD.1 (ME Contractor)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0287
  - P0288
  - P0298
  - P0299
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0068
  from: FCP-RD
  to: DOAS-RD.2 (BMS Contractor)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 8
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 6
  carries_point_ids:
  - P0309
  - P0310
  - P0311
  - P0325
  - P0326
  - '...'
  notes: 6 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0069
  from: FCP-RD
  to: DOAS-RD.2 (Equipment Supplier)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 12
  conductor_count_specified: 12
  length_m: 30
  carries_io_points: 10
  carries_point_ids:
  - P0314
  - P0315
  - P0316
  - P0317
  - P0318
  - '...'
  notes: 10 I/O points carried, 12C cable per A-001 (avg 30 m)
- id: C0070
  from: FCP-RD
  to: DOAS-RD.2 (ME Contractor)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0312
  - P0313
  - P0323
  - P0324
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0071
  from: FCP-GF
  to: EF-1.2A (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0380
  - P0381
  - P0382
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0072
  from: FCP-GF
  to: EF-1MR.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0386
  - P0387
  - P0388
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0073
  from: FCP-GF
  to: EF-1ST0.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0389
  - P0390
  - P0391
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0074
  from: FCP-2F
  to: EF-2.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0416
  - P0417
  - P0418
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0075
  from: FCP-2F
  to: EF-2.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0419
  - P0420
  - P0421
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0076
  from: FCP-2F
  to: EF-2.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0422
  - P0423
  - P0424
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0077
  from: FCP-2F
  to: EF-2.4 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0425
  - P0426
  - P0427
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0078
  from: FCP-2F
  to: EF-2B.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0404
  - P0405
  - P0406
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0079
  from: FCP-2F
  to: EF-2B.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0407
  - P0408
  - P0409
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0080
  from: FCP-3F
  to: EF-3GE.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0509
  - P0510
  - P0511
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0081
  from: FCP-3F
  to: EF-3GE.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0512
  - P0513
  - P0514
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0082
  from: FCP-2F
  to: EF-CHR.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0428
  - P0429
  - P0430
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0083
  from: FCP-2F
  to: EF-CHR.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0431
  - P0432
  - P0433
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0084
  from: FCP-2F
  to: EF-GS.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0410
  - P0411
  - P0412
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0085
  from: FCP-2F
  to: EF-GS.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0413
  - P0414
  - P0415
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0086
  from: FCP-GF
  to: EF-LPG.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0383
  - P0384
  - P0385
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0087
  from: FCP-GF
  to: EF-MRF.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0392
  - P0393
  - P0394
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0088
  from: FCP-BSMT
  to: GEN-1 (EE Contractor)
  equipment_class: Multifunction Power Meter (Main)
  system: EE
  location: Basement (Genset)
  cable_type: "Modbus shielded twisted-pair, 1pr \xD7 22 AWG (e.g., Belden 9841)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0758
  - P0759
  - P0760
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0089
  from: FCP-RD
  to: HP-HZ.1 (Equipment Supplier)
  equipment_class: Heat Pump
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0722
  - P0723
  - P0724
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0090
  from: FCP-RD
  to: HP-HZ.2 (Equipment Supplier)
  equipment_class: Heat Pump
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0725
  - P0726
  - P0727
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0091
  from: FCP-RD
  to: HP-HZ.3 (Equipment Supplier)
  equipment_class: Heat Pump
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0728
  - P0729
  - P0730
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0092
  from: FCP-BSMT
  to: HP-LZ.1 (Equipment Supplier)
  equipment_class: Heat Pump
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0713
  - P0714
  - P0715
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0093
  from: FCP-BSMT
  to: HP-LZ.2 (Equipment Supplier)
  equipment_class: Heat Pump
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0716
  - P0717
  - P0718
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0094
  from: FCP-BSMT
  to: HP-LZ.3 (Equipment Supplier)
  equipment_class: Heat Pump
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0719
  - P0720
  - P0721
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0095
  from: FCP-RD
  to: HW-HDR-HZ (BMS Contractor)
  equipment_class: Hot Water Header Set
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0710
  - P0711
  - P0712
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0096
  from: FCP-BSMT
  to: HW-HDR-LZ (BMS Contractor)
  equipment_class: Hot Water Header Set
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0707
  - P0708
  - P0709
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0097
  from: FCP-RD
  to: HWT-HZ.1 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0704
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0098
  from: FCP-RD
  to: HWT-HZ.2 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0705
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0099
  from: FCP-RD
  to: HWT-HZ.3 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0706
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0100
  from: FCP-BSMT
  to: HWT-LZ.1 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0701
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0101
  from: FCP-BSMT
  to: HWT-LZ.2 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0702
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0102
  from: FCP-BSMT
  to: HWT-LZ.3 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0703
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0103
  from: FCP-2F
  to: ION-2M.1 (BMS Contractor)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0364
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0104
  from: FCP-2F
  to: ION-2M.1 (Equipment Supplier)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0362
  - P0363
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0105
  from: FCP-2F
  to: ION-2M.2 (BMS Contractor)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 3
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0367
  notes: 1 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0106
  from: FCP-2F
  to: ION-2M.2 (Equipment Supplier)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: AC
  location: 2nd Floor (Casino)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0365
  - P0366
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0107
  from: FCP-BSMT
  to: PAHU-0.1 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Basement
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0141
  - P0142
  - P0143
  - P0153
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0108
  from: FCP-BSMT
  to: PAHU-0.1 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Basement
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0144
  - P0145
  - P0148
  - P0149
  - P0150
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0109
  from: FCP-BSMT
  to: PAHU-0.1 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Basement
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0146
  - P0147
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0110
  from: FCP-2F
  to: PAHU-B1 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0155
  - P0156
  - P0157
  - P0167
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0111
  from: FCP-2F
  to: PAHU-B1 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0158
  - P0159
  - P0162
  - P0163
  - P0164
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0112
  from: FCP-2F
  to: PAHU-B1 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0160
  - P0161
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0113
  from: FCP-2F
  to: PAHU-B2 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0169
  - P0170
  - P0171
  - P0181
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0114
  from: FCP-2F
  to: PAHU-B2 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0172
  - P0173
  - P0176
  - P0177
  - P0178
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0115
  from: FCP-2F
  to: PAHU-B2 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0174
  - P0175
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0116
  from: FCP-2F
  to: PAHU-B3 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0183
  - P0184
  - P0185
  - P0195
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0117
  from: FCP-2F
  to: PAHU-B3 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0186
  - P0187
  - P0190
  - P0191
  - P0192
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0118
  from: FCP-2F
  to: PAHU-B3 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0188
  - P0189
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0119
  from: FCP-2F
  to: PAHU-FR (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0211
  - P0212
  - P0213
  - P0223
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0120
  from: FCP-2F
  to: PAHU-FR (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0214
  - P0215
  - P0218
  - P0219
  - P0220
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0121
  from: FCP-2F
  to: PAHU-FR (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0216
  - P0217
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0122
  from: FCP-2F
  to: PAHU-PF (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0197
  - P0198
  - P0199
  - P0209
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0123
  from: FCP-2F
  to: PAHU-PF (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0200
  - P0201
  - P0204
  - P0205
  - P0206
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0124
  from: FCP-2F
  to: PAHU-PF (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0202
  - P0203
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0125
  from: FCP-RD
  to: PAHU-RD.1 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0334
  - P0335
  - P0336
  - P0346
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0126
  from: FCP-RD
  to: PAHU-RD.1 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0337
  - P0338
  - P0341
  - P0342
  - P0343
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0127
  from: FCP-RD
  to: PAHU-RD.1 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0339
  - P0340
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0128
  from: FCP-RD
  to: PAHU-RD.2 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 shielded FRLS (BMS signal \u2014 sensors)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0348
  - P0349
  - P0350
  - P0360
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0129
  from: FCP-RD
  to: PAHU-RD.2 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 7
  conductor_count_specified: 8
  length_m: 30
  carries_io_points: 5
  carries_point_ids:
  - P0351
  - P0352
  - P0355
  - P0356
  - P0357
  notes: 5 I/O points carried, 8C cable per A-001 (avg 30 m)
- id: C0130
  from: FCP-RD
  to: PAHU-RD.2 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (ME-supplied valves/dampers \u2014 status + control)"
  conductor_count_required: 4
  conductor_count_specified: 4
  length_m: 30
  carries_io_points: 2
  carries_point_ids:
  - P0353
  - P0354
  notes: 2 I/O points carried, 4C cable per A-001 (avg 30 m)
- id: C0131
  from: MCP-PLANT
  to: PCHW-1 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0605
  - P0606
  - P0607
  - P0609
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0132
  from: MCP-PLANT
  to: PCHW-2 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0610
  - P0611
  - P0612
  - P0614
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0133
  from: MCP-PLANT
  to: PCHW-3 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0615
  - P0616
  - P0617
  - P0619
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0134
  from: MCP-PLANT
  to: PCHW-S (Equipment Supplier)
  equipment_class: Primary CHW Pump (Standby)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 6
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 4
  carries_point_ids:
  - P0620
  - P0621
  - P0622
  - P0624
  notes: 4 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0135
  from: MCP-PLANT
  to: PCOW-1 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0625
  - P0626
  - P0627
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0136
  from: MCP-PLANT
  to: PCOW-2 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0628
  - P0629
  - P0630
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0137
  from: MCP-PLANT
  to: PCOW-3 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0631
  - P0632
  - P0633
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0138
  from: FCP-RD
  to: RP-HZ.1 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0740
  - P0741
  - P0742
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0139
  from: FCP-RD
  to: RP-HZ.2 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0743
  - P0744
  - P0745
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0140
  from: FCP-RD
  to: RP-HZ.3 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: HWL
  location: Roofdeck
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0746
  - P0747
  - P0748
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0141
  from: FCP-BSMT
  to: RP-LZ.1 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0731
  - P0732
  - P0733
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0142
  from: FCP-BSMT
  to: RP-LZ.2 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0734
  - P0735
  - P0736
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0143
  from: FCP-BSMT
  to: RP-LZ.3 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: HWL
  location: Lower Ground
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0737
  - P0738
  - P0739
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0144
  from: FCP-GF
  to: TEF-1.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0368
  - P0369
  - P0370
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0145
  from: FCP-GF
  to: TEF-1.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0371
  - P0372
  - P0373
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0146
  from: FCP-GF
  to: TEF-1.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0374
  - P0375
  - P0376
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0147
  from: FCP-GF
  to: TEF-1.4 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: Ground Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0377
  - P0378
  - P0379
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0148
  from: FCP-2F
  to: TEF-2.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0395
  - P0396
  - P0397
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0149
  from: FCP-2F
  to: TEF-2.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0398
  - P0399
  - P0400
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0150
  from: FCP-2F
  to: TEF-2B.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 2nd Floor
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0401
  - P0402
  - P0403
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0151
  from: FCP-3F
  to: TEF-3A.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0434
  - P0435
  - P0436
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0152
  from: FCP-3F
  to: TEF-3A.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0437
  - P0438
  - P0439
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0153
  from: FCP-3F
  to: TEF-3B.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0440
  - P0441
  - P0442
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0154
  from: FCP-3F
  to: TEF-3C.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0443
  - P0444
  - P0445
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0155
  from: FCP-3F
  to: TEF-3C.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Amenity)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0446
  - P0447
  - P0448
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0156
  from: FCP-3F
  to: TEF-3D.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0449
  - P0450
  - P0451
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0157
  from: FCP-3F
  to: TEF-3D.10 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0476
  - P0477
  - P0478
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0158
  from: FCP-3F
  to: TEF-3D.11 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0479
  - P0480
  - P0481
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0159
  from: FCP-3F
  to: TEF-3D.12 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0482
  - P0483
  - P0484
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0160
  from: FCP-3F
  to: TEF-3D.13 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0485
  - P0486
  - P0487
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0161
  from: FCP-3F
  to: TEF-3D.14 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0488
  - P0489
  - P0490
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0162
  from: FCP-3F
  to: TEF-3D.15 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0491
  - P0492
  - P0493
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0163
  from: FCP-3F
  to: TEF-3D.16 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0494
  - P0495
  - P0496
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0164
  from: FCP-3F
  to: TEF-3D.17 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0497
  - P0498
  - P0499
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0165
  from: FCP-3F
  to: TEF-3D.18 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0500
  - P0501
  - P0502
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0166
  from: FCP-3F
  to: TEF-3D.19 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0503
  - P0504
  - P0505
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0167
  from: FCP-3F
  to: TEF-3D.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0452
  - P0453
  - P0454
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0168
  from: FCP-3F
  to: TEF-3D.20 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0506
  - P0507
  - P0508
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0169
  from: FCP-3F
  to: TEF-3D.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0455
  - P0456
  - P0457
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0170
  from: FCP-3F
  to: TEF-3D.4 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0458
  - P0459
  - P0460
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0171
  from: FCP-3F
  to: TEF-3D.5 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0461
  - P0462
  - P0463
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0172
  from: FCP-3F
  to: TEF-3D.6 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0464
  - P0465
  - P0466
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0173
  from: FCP-3F
  to: TEF-3D.7 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0467
  - P0468
  - P0469
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0174
  from: FCP-3F
  to: TEF-3D.8 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0470
  - P0471
  - P0472
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0175
  from: FCP-3F
  to: TEF-3D.9 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: VENT
  location: 3rd Floor (Guestroom)
  cable_type: "4C \xD7 1.5 mm\xB2 FRLS (equipment aux contacts \u2014 status/HOA/trip)"
  conductor_count_required: 5
  conductor_count_specified: 6
  length_m: 30
  carries_io_points: 3
  carries_point_ids:
  - P0473
  - P0474
  - P0475
  notes: 3 I/O points carried, 6C cable per A-001 (avg 30 m)
- id: C0176
  from: FCP-BSMT
  to: PAHU-0.1 (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Basement
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0154
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0177
  from: FCP-2F
  to: PAHU-B1 (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0168
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0178
  from: FCP-2F
  to: PAHU-B2 (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0182
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0179
  from: FCP-2F
  to: PAHU-B3 (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0196
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0180
  from: FCP-2F
  to: PAHU-PF (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0210
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0181
  from: FCP-2F
  to: PAHU-FR (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0224
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0182
  from: FCP-2F
  to: DOAS-2M (Network)
  equipment_class: DOAS Unit
  system: VENT
  location: 2nd Floor (Casino)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0283
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0183
  from: FCP-RD
  to: DOAS-RD.1 (Network)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0308
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0184
  from: FCP-RD
  to: DOAS-RD.2 (Network)
  equipment_class: DOAS Unit
  system: VENT
  location: Roofdeck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0333
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0185
  from: FCP-RD
  to: PAHU-RD.1 (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0347
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0186
  from: FCP-RD
  to: PAHU-RD.2 (Network)
  equipment_class: Precooled Air Handling Unit
  system: VENT
  location: Roofdeck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0361
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0187
  from: MCP-PLANT
  to: CH-1 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0544
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0188
  from: MCP-PLANT
  to: CH-2 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0574
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0189
  from: MCP-PLANT
  to: CH-3 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: AC
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0604
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0190
  from: MCP-PLANT
  to: PM-MAIN (Network)
  equipment_class: Multifunction Power Meter (Main)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0749
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0191
  from: MCP-PLANT
  to: PM-GEN (Network)
  equipment_class: Multifunction Power Meter (Main)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0750
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0192
  from: MCP-PLANT
  to: PM-MCC-CHILLER (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0751
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0193
  from: MCP-PLANT
  to: PM-MCC-CT (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0752
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0194
  from: MCP-PLANT
  to: PM-MCC-BOILER (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0753
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0195
  from: MCP-PLANT
  to: PM-MCC-FIRE-PUMP (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0754
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0196
  from: MCP-PLANT
  to: PM-MCC-MDP-1 (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0755
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0197
  from: MCP-PLANT
  to: PM-MCC-MDP-2 (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0756
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
- id: C0198
  from: MCP-PLANT
  to: PM-MCC-MDP-3 (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: EE
  location: 2nd Floor (Plant Room)
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 30
  carries_io_points: 1
  carries_point_ids:
  - P0757
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller"
trunk_cables:
- id: T0199
  from: BMS Server Room (head-end)
  to: All BMS panels at 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for 2nd Floor \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0200
  from: BMS Server Room (head-end)
  to: All BMS panels at 3rd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for 3rd Floor \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0201
  from: BMS Server Room (head-end)
  to: All BMS panels at Basement
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Basement \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0202
  from: BMS Server Room (head-end)
  to: All BMS panels at Ground
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Ground \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0203
  from: BMS Server Room (head-end)
  to: All BMS panels at Lower Ground
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Lower Ground \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0204
  from: BMS Server Room (head-end)
  to: All BMS panels at Roofdeck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Roofdeck \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0205
  from: BMS Server Room (head-end)
  to: All BMS panel controllers (MS/TP daisy-chain or branched)
  cable_type: "BACnet MS/TP shielded twisted-pair trunk, 1pr \xD7 22 AWG low-cap"
  length_m: 180
  notes: "MS/TP backbone interconnecting 6 BMS panels \u2014 refine after Q-008 layout review"
panel_power_feeds:
- id: P0206
  from: Local panelboard / EE-supplied feeder
  to: "FCP-2F \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 30
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
- id: P0207
  from: Local panelboard / EE-supplied feeder
  to: "FCP-3F \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 30
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
- id: P0208
  from: Local panelboard / EE-supplied feeder
  to: "FCP-BSMT \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 30
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
- id: P0209
  from: Local panelboard / EE-supplied feeder
  to: "FCP-GF \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 30
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
- id: P0210
  from: Local panelboard / EE-supplied feeder
  to: "FCP-RD \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 30
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
- id: P0211
  from: Local panelboard / EE-supplied feeder
  to: "MCP-PLANT \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 30
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)