# A2 — Equipment Takeoff
# Generated from A1-io-list.yaml on $(date) — see metadata.generator
# Schema: see _playbook/checklists/working-documents.md (A2)
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS Rehabilitation (A/B run)"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a2-equipment-takeoff.py
  regenerate: Re-run the generator after A1 changes. Hand edits to make_model_assumed and notes can be preserved by editing equipment-class-defaults.yaml or adding per-instance overrides below.
summary:
  total_instances: 125
  by_equipment_class:
    Exhaust Fan (Toilet): 32
    Exhaust Fan (General): 17
    AHU (Chilled-Water-Served): 10
    Precooled Air Handling Unit: 8
    Multifunction Power Meter (Feeder): 7
    Heat Pump: 6
    Calorifier (Hot Water Storage Tank): 6
    Recirculating Pump: 6
    Multifunction Power Meter (Main): 4
    Chiller (Package Water-Cooled): 3
    Cooling Tower: 3
    DOAS Unit: 3
    Primary CHW Pump: 3
    Condenser Water Pump: 3
    AHU (Modulating CHW-served): 2
    Steam Boiler: 2
    Hot Water Header Set: 2
    Ozone Generator (UV-light or Corona): 2
    CHW Bypass Header: 1
    CHW Return Main Header: 1
    CHW Supply Main Header: 1
    Condenser Water Header: 1
    Cooling Tower (Common): 1
    Primary CHW Pump (Standby): 1
  by_location:
    2nd Floor: 25
    2nd Floor (Plant Room): 22
    3rd Floor (Guestroom): 20
    Roofdeck: 19
    Ground Floor: 12
    Lower Ground: 12
    3rd Floor (Amenity): 7
    2nd Floor (Casino): 5
    Basement (Genset): 2
    Basement: 1
  by_panel:
    FCP-2F: 30
    FCP-3F: 27
    MCP-PLANT: 22
    FCP-RD: 19
    FCP-BSMT: 15
    FCP-GF: 12
  by_primary_co:
    Equipment Supplier: 96
    BMS Contractor: 27
    EE Contractor: 2
takeoff:
- id: AHU-1.1
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Ground Floor
  system: AC
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-1.2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Ground Floor
  system: AC
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-1.3
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Ground Floor
  system: AC
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-2M.1
  equipment_class: AHU (Modulating CHW-served)
  quantity: 1
  location: 2nd Floor (Casino)
  system: AC
  panel: FCP-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 15
    hli_subpoints: 2
    network_drops: 0
    total: 17
    by_type:
      AI: 8
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 8
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: "Casino-spec AHU \u2014 modulating actuators with position feedback; CO/CO2 monitoring at return duct."
- id: AHU-2M.2
  equipment_class: AHU (Modulating CHW-served)
  quantity: 1
  location: 2nd Floor (Casino)
  system: AC
  panel: FCP-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 15
    hli_subpoints: 2
    network_drops: 0
    total: 17
    by_type:
      AI: 8
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 8
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: "Casino-spec AHU \u2014 modulating actuators with position feedback; CO/CO2 monitoring at return duct."
- id: AHU-B.1
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-B.2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-B.3
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-EL
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-FR2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-FR3
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-PF
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Floor
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 5
      AO: 3
      DI: 4
      HLI: 2
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 6
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: ATS-1
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: Basement (Genset)
  system: EE
  panel: FCP-BSMT
  primary_co: EE Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      EE Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: BLR-1
  equipment_class: Steam Boiler
  quantity: 1
  location: Lower Ground
  system: VENT
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 16
    hli_subpoints: 0
    network_drops: 0
    total: 16
    by_type:
      AI: 4
      AO: 1
      DI: 11
    by_co:
      BMS Contractor: 6
      Equipment Supplier: 10
  make_model_assumed: Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
- id: BLR-2
  equipment_class: Steam Boiler
  quantity: 1
  location: Lower Ground
  system: VENT
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 16
    hli_subpoints: 0
    network_drops: 0
    total: 16
    by_type:
      AI: 4
      AO: 1
      DI: 11
    by_co:
      BMS Contractor: 6
      Equipment Supplier: 10
  make_model_assumed: Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
- id: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 18
    network_drops: 1
    total: 30
    by_type:
      AI: 7
      DI: 4
      HLI: 18
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 19
      ME Contractor: 4
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 18
    network_drops: 1
    total: 30
    by_type:
      AI: 7
      DI: 4
      HLI: 18
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 19
      ME Contractor: 4
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 18
    network_drops: 1
    total: 30
    by_type:
      AI: 7
      DI: 4
      HLI: 18
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 19
      ME Contractor: 4
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CHW-BYPASS
  equipment_class: CHW Bypass Header
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      AI: 2
      AO: 1
      DI: 1
    by_co:
      BMS Contractor: 4
  make_model_assumed: BMS dP/dT sensors + motorized bypass valve (BMS-supplied)
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: BMS controls bypass valve to maintain CHW differential.
- id: CHW-HDR-R
  equipment_class: CHW Return Main Header
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: BMS T+P sensors on CHW return manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: CHW-HDR-S
  equipment_class: CHW Supply Main Header
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: BMS T+P sensors on CHW supply manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: COW-HDR
  equipment_class: Condenser Water Header
  quantity: 1
  location: Roofdeck
  system: AC
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: BMS T sensors on condenser water headers at roofdeck
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: CT-1
  equipment_class: Cooling Tower
  quantity: 1
  location: Roofdeck
  system: AC
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 7
    hli_subpoints: 0
    network_drops: 0
    total: 7
    by_type:
      AI: 1
      AO: 1
      DI: 5
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 2
      ME Contractor: 2
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-2
  equipment_class: Cooling Tower
  quantity: 1
  location: Roofdeck
  system: AC
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 7
    hli_subpoints: 0
    network_drops: 0
    total: 7
    by_type:
      AI: 1
      AO: 1
      DI: 5
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 2
      ME Contractor: 2
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-3
  equipment_class: Cooling Tower
  quantity: 1
  location: Roofdeck
  system: AC
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 7
    hli_subpoints: 0
    network_drops: 0
    total: 7
    by_type:
      AI: 1
      AO: 1
      DI: 5
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 2
      ME Contractor: 2
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-COMMON
  equipment_class: Cooling Tower (Common)
  quantity: 1
  location: Roofdeck
  system: AC
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      AI: 4
    by_co:
      BMS Contractor: 4
  make_model_assumed: Common BMS sensors at cooling tower area (OA T/RH, condenser headers)
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: "Field instrumentation only \u2014 no equipment per se."
- id: DOAS-2M
  equipment_class: DOAS Unit
  quantity: 1
  location: 2nd Floor (Casino)
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 20
    hli_subpoints: 4
    network_drops: 1
    total: 25
    by_type:
      AI: 8
      AO: 2
      DI: 10
      HLI: 4
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 14
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: DOAS-RD.1
  equipment_class: DOAS Unit
  quantity: 1
  location: Roofdeck
  system: VENT
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 20
    hli_subpoints: 4
    network_drops: 1
    total: 25
    by_type:
      AI: 8
      AO: 2
      DI: 10
      HLI: 4
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 14
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: DOAS-RD.2
  equipment_class: DOAS Unit
  quantity: 1
  location: Roofdeck
  system: VENT
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 20
    hli_subpoints: 4
    network_drops: 1
    total: 25
    by_type:
      AI: 8
      AO: 2
      DI: 10
      HLI: 4
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 14
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: EF-1.2A
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-1MR.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-1ST0.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.3
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.4
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2B.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2B.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3GE.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3GE.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-CHR.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-CHR.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-GS.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-GS.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-LPG.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-MRF.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: GEN-1
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: Basement (Genset)
  system: EE
  panel: FCP-BSMT
  primary_co: EE Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      EE Contractor: 3
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: HP-HZ.1
  equipment_class: Heat Pump
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-HZ.2
  equipment_class: Heat Pump
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-HZ.3
  equipment_class: Heat Pump
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-LZ.1
  equipment_class: Heat Pump
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-LZ.2
  equipment_class: Heat Pump
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-LZ.3
  equipment_class: Heat Pump
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HW-HDR-HZ
  equipment_class: Hot Water Header Set
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensor
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation on existing piping.
- id: HW-HDR-LZ
  equipment_class: Hot Water Header Set
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensor
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation on existing piping.
- id: HWT-HZ.1
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: HWT-HZ.2
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: HWT-HZ.3
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: HWT-LZ.1
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: HWT-LZ.2
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: HWT-LZ.3
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: ION-2M.1
  equipment_class: Ozone Generator (UV-light or Corona)
  quantity: 1
  location: 2nd Floor (Casino)
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 1
      DI: 2
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 2
  make_model_assumed: UV-light or corona-discharge ozone generator (paired with Casino AHU)
  network_type: Hardwired
  typical_supplier: Equipment supplier
  notes: Casino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
- id: ION-2M.2
  equipment_class: Ozone Generator (UV-light or Corona)
  quantity: 1
  location: 2nd Floor (Casino)
  system: AC
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 1
      DI: 2
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 2
  make_model_assumed: UV-light or corona-discharge ozone generator (paired with Casino AHU)
  network_type: Hardwired
  typical_supplier: Equipment supplier
  notes: Casino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
- id: PAHU-0.1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Basement
  system: VENT
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-B1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-B2
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-B3
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-FR
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-PF
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-RD.1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Roofdeck
  system: VENT
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-RD.2
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Roofdeck
  system: VENT
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 11
    hli_subpoints: 2
    network_drops: 1
    total: 14
    by_type:
      AI: 4
      AO: 2
      DI: 5
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PCHW-1
  equipment_class: Primary CHW Pump
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 1
    network_drops: 0
    total: 5
    by_type:
      AI: 1
      DI: 3
      HLI: 1
    by_co:
      Equipment Supplier: 5
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: PCHW-2
  equipment_class: Primary CHW Pump
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 1
    network_drops: 0
    total: 5
    by_type:
      AI: 1
      DI: 3
      HLI: 1
    by_co:
      Equipment Supplier: 5
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: PCHW-3
  equipment_class: Primary CHW Pump
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 1
    network_drops: 0
    total: 5
    by_type:
      AI: 1
      DI: 3
      HLI: 1
    by_co:
      Equipment Supplier: 5
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: PCHW-S
  equipment_class: Primary CHW Pump (Standby)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 1
    network_drops: 0
    total: 5
    by_type:
      AI: 1
      DI: 3
      HLI: 1
    by_co:
      Equipment Supplier: 5
  make_model_assumed: Same as Primary CHW Pump (1 standby for N+1 redundancy)
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: Standby unit per A-CHW-001.
- id: PCOW-1
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: PCOW-2
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: PCOW-3
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: AC
  panel: MCP-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: PM-GEN
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: PM-MAIN
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: PM-MCC-BOILER
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: PM-MCC-CHILLER
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: PM-MCC-CT
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: PM-MCC-FIRE-PUMP
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: PM-MCC-MDP-1
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: PM-MCC-MDP-2
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: PM-MCC-MDP-3
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Floor (Plant Room)
  system: EE
  panel: MCP-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: RP-HZ.1
  equipment_class: Recirculating Pump
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-HZ.2
  equipment_class: Recirculating Pump
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-HZ.3
  equipment_class: Recirculating Pump
  quantity: 1
  location: Roofdeck
  system: HWL
  panel: FCP-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-LZ.1
  equipment_class: Recirculating Pump
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-LZ.2
  equipment_class: Recirculating Pump
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-LZ.3
  equipment_class: Recirculating Pump
  quantity: 1
  location: Lower Ground
  system: HWL
  panel: FCP-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: TEF-1.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-1.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-1.3
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-1.4
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: Ground Floor
  system: VENT
  panel: FCP-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2.3
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2B.3
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: FCP-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3A.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3A.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3B.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3C.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3C.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Amenity)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.10
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.11
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.12
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.13
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.14
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.15
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.16
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.17
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.18
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.19
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.20
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.3
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.4
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.5
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.6
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.7
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.8
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3D.9
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor (Guestroom)
  system: VENT
  panel: FCP-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."