# Instance: Programming & Engineering for Kingsford Hotel Bacolod (A/B run)

**WBS leaves served:** 4.1, 4.2, 4.3, 4.4, 4.5, 4.6
**Module ref:** `_playbook/modules/bms/programming-engineering.md`

## Project-specific parameter values

From B1 / B2:
- Programming objects total: **1,366**
- Programming hours: **254.8 hr** (from helper)
- Graphics pages: 14, total **198 graphics hours**
- Integration drivers: BACnet/IP (chillers, DOAS), BACnet MS/TP (where vendor uses), Modbus RTU (power meters), hardwired (everything else)

## Sequences

Per DRC-004 description-of-operations, key sequences to program:
1. Chiller plant optimization (lead-lag, staging, kW/TR)
2. Primary CHW pump VFD speed control on differential pressure
3. Cooling tower fan staging on COW supply T
4. AHU cascade (return-air CO₂ → OA damper; supply-air T → CHW valve; supply-air RH → reheat)
5. DOAS heat recovery wheel staging (OA T/RH vs. exhaust T/RH)
6. Calorifier hot-water staging (return T setpoint, HP/RP enable)
7. Boiler firing rate (small/big fire) per steam pressure setpoint, water level safeties
8. Casino AHU + ionizer interlock (ionizer enable when AHU-2M.1/2M.2 running)
9. Power-event response (alarm broadcast, equipment auto-restart sequencing on genset)

## BOQ line items

Per module template × hours from B1 + B2.

## Cross-references

- Working docs: A1, A2, B1, B2, B3
- Assumptions: A-013 (graphics ≈14)
- Clarifications: Q-004 (vendor)