# Instance: BMS Head-End for Kingsford Hotel Bacolod (A/B run)

**WBS leaves served:** 2.1.1–2.1.6, 3.7
**Module ref:** `_playbook/modules/bms/head-end.md`

## Project-specific parameter values

- Server class: 1× tier-1 OEM server, 6-core Xeon, 16 GB RAM, 2× 1 TB SSD RAID-1
- Workstations: 2× operator-grade i7 with dual 24″ monitors (engineering + operator)
- Software licenses sized for 1500-point capacity (≈800 actual + 50% headroom)
- UPS: 1.5 kVA online, 30-min runtime
- Rack: 12U wall-mount in 2nd Floor Plant Room

## BOQ line items

See `A6-head-end-equipment.yaml` for the canonical line items.

## Open assumptions

A-004 (vendor), A-013 (graphics ≈14 pages — drives capacity sizing).

## Cross-references

- Working doc: `A6-head-end-equipment.yaml`, `A5-network-architecture.md`
- Assumptions: A-003, A-004, A-013
- Clarifications: Q-004, Q-008