# A4 — Panel Schedule
# For our scope: limited to OCC + FCCR rack/cabinet sizing. Station + depot panels are Civil Contractor scope (D-017).

metadata:
  project: "SMC MRT-7 FDAS+ACS Integration"
  date: "2026-04-29"
  source: "Resp. Matrix + ANNEX_C1 §1123.2.8 / §1124.2.6 / §1124.2.8"
  status: draft

panels:
  - id: P-001
    name: "OCC FDAS Server Rack"
    location: "OCC, Depot Admin Building"
    type: "42U server rack"
    contents:
      - "FDAS Workstation PC (rack-mount option)"
      - "FDAS Server (4U rackmount)"
      - "L2 Industrial Ethernet Switch (1U DIN/rack)"
      - "UPS 2 kVA (3U rackmount)"
      - "Patch panel (1U) for FOC + Cat6A"
      - "Cable management arms"
    power_feed_source: "Civil Contractor ECB at OCC (230 V dedicated)"
    network_drop_count: 6  # WS + server + printer + UPS-SNMP + uplink-to-CER + spare
    dimensions_estimated: "600 mm W × 1000 mm D × 2000 mm H (42U)"
    notes: "Per ANNEX_C1 §1123.2.8 — rackmount or desktop allowed; rack assumed for unified install"
  - id: P-002
    name: "OCC ACS Server Rack"
    location: "OCC, Depot Admin Building"
    type: "42U server rack (separate per A-106)"
    contents:
      - "ACS Workstation PC"
      - "ACS Server (with SQL Server)"
      - "L2 Switch with SFP"
      - "UPS 2 kVA"
      - "Badge printer (or table-top adjacent)"
      - "Patch panel (FOC + Cat6A)"
    power_feed_source: "Civil Contractor ECB"
    network_drop_count: 6
  - id: P-003
    name: "FCCR FDAS Server Rack"
    location: "FCCR, Depot Admin Building"
    type: "42U server rack"
    contents: "Same as P-001"
    power_feed_source: "Civil Contractor ECB at FCCR"
    network_drop_count: 6
  - id: P-004
    name: "FCCR ACS Server Rack"
    location: "FCCR, Depot Admin Building"
    type: "42U server rack"
    contents: "Same as P-002"
    power_feed_source: "Civil Contractor ECB at FCCR"
    network_drop_count: 6

# Note: at each station + each depot integration building, our gateway mounts in the
# per-station/per-building contractor's existing FACP/CS-40 cabinet or in a wall-mounted
# enclosure adjacent to it. Not enumerated as a separate "panel" in our schedule.
# Workstation operator-furniture (table) is in A6 (not in panel schedule).

summary:
  total_panels_in_our_scope: 4
  total_42U_racks: 4
  total_network_drops_at_head_ends: 24  # 6 × 4 racks
  notes: |
    Panel count is limited to head-end rack inventory at OCC + FCCR per Resp. Matrix.
    Per A-106, we use separate FDAS + ACS racks for fault isolation (configurable to combined VLAN-shared rack at NTP if customer prefers).
    Rack siting at OCC + FCCR refined at site survey post-NTP (Q-012 closed; specifics from site visit notes).